目录
1.1工程概况:.............................................................................................................12.1选型及结构布置.....................................................................................................2
2.1.1确定楼盖类型......................................................................................22.1.2建筑及结构布置图.....................................................................32.1.3荷载计算...............................................................................................42.1.4初选确定杆件截面尺寸.....................................................................6
2.2结构计算简图........................................................................................................9
2.2.1计算简图............................................................................................9
2.3.内力计算..............................................................................................................26
2.3.1框架在竖向力作用下的内力计算....................................................26
2.4.内力组合..............................................................................................................31
2.4.1框架梁内力组合..............................................................................322.4.2框架柱内力组合..............................................................................35
2.5结构、构件截面验算........................................................................................35
2.5.1框架柱截面验算................................................................................352.5.2框架横梁验算.....................................................................................502.5.3次梁验算..........................................................................................53
2.6组合楼盖设计....................................................................................................55
2.6.1楼板设计..........................................................................................552.6.2屋面板设计......................................................................................60
2.7框架连接设计....................................................................................................65
2.7.1主梁与柱的连接设计......................................................................652.7.2次梁与主梁的连接设计..................................................................742.7.3柱脚设计..........................................................................................782.7.4柱与柱连接设计..............................................................................82
2.8基础设计............................................................................................................82
2.8.1A柱基础设计...................................................................................822.8.2B柱基础设计...................................................................................88
2.9楼梯设计..............................................................................................................92
2.9.1梯段板的计算.....................................................................................922.9.2平台板的计算.....................................................................................932.9.3平台梁的计算.....................................................................................94
参考文献.........................................................................................................................................98
1
文天学院2012届本科生毕业设计(论文)
1工程概况:1.1.1
⑴、工程名称:腾讯仪表厂二号楼厂房(C方案)设计⑵、建筑面积:3240平方米⑶、结构型式:钢框架结构⑷、总层数为三层,无地下室⑸、抗震设防烈度7度,近震
⑹、建筑场地Ⅱ类,基本风压W0=0.40KN/m2,基本雪压S0=0.65KN/m2,⑺、地面粗糙度B类
⑻、层高:首层6.48米,标准层4.5米
⑼、钢材等级:主次梁采用热轧H型钢梁(Q235型钢),柱子焊接工字型截面⑽、基础型式:柱下基础
⑾、地质条件:天然地基,以粉质粘土为持力层,基础埋深1.5米。
南京江宁地区地基承载力的特征值fak=250kpa⑿、建筑物等级:二级⒀、耐火等级:二级
2.1选型及结构布置2.1.1确定楼盖类型
据《抗震规范》8.1.7条,宜采用压型钢板现浇钢筋砼组合楼板或非组合楼板,目前国内多采用非组合楼板(简支梁类构件楼盖除外)。非组合楼板中的压型钢板只起到施工阶段的模板作用,按施工阶段的两种极限状态要求确定压型钢板几何形状和厚度,可采用国内生产的无齿痕的压型板,不需作防火层(但需防锈,宜采用镀锌板),仅楼板的端部按构造设置圆头栓钉。采用非组合楼盖也给手算带来很大方便,又适应国内发展形势,因此选择采用非组合楼板。根据板的跨度和非组合板的厚度,选择国产压型钢板型号:YX-75-230-690(Ⅱ)。另外,为方便手算,采用主次梁单向板肋形楼盖布置形式。计算时,框架梁在确定截面惯性矩时,对于非组合楼板,由于钢板上的现浇混凝土板和压型钢板结合不够紧密,板的约束很微弱,
2
文天学院2012届本科生毕业设计(论文)
因此,直接取钢梁的截面惯性矩Ib,不考虑板的影响。
2.1.2建筑及结构布置图
建筑平面图1
结构布置图2
3
截 面 表
文天学院2012届本科生毕业设计(论文)
2.1.3荷载计算
①.屋面荷载计算
恒载:
SBS改性沥青高分子防水卷材一层(三毡四油)1:3水泥砂浆找平层20mm
40厚细石混凝土面层(每两米设一分仓缝)保温层200mm
20厚1:3水泥砂浆找平层
0.4 KN/m
2
20×0.02=0.4KN/m2
24×0.04=0.96 KN/m2
8×0.2=1.6 KN/m220×0.02=0.4KN/m
2
非组合楼盖(压型钢板-选用YX-75-230-690,上混凝土层厚80mm)
25×0.10=2.50 KN/m2
压型钢板总计
活载:(按照不上人屋面设计取荷载标准值)
0.18KN/m
2
6.440KN/m20.50KN/m
2
②.楼面荷载计算1)生产车间荷载计算恒载:
15厚1:2白水泥白石子10厚素水泥浆结合层一道20厚1:3水泥砂浆找平层
25×0.015=0.3KN/m
2
20×0.010=0.2KN/m
20×0.02=0.4KN/m
2
2
非组合楼盖(压型钢板-选用YX-75-230-690,上混凝土层厚80mm)
25×0.01=0.25KN/m
2
0.18KN/m
压型钢板总计
4
2
3.58KN/m
2
文天学院2012届本科生毕业设计(论文)
活载:
4.0KN/m
2
2)其它房间:
i:更衣室、值班室、门厅荷载计算15厚1:2白水泥白石子10厚素水泥浆结合层一道20厚1:3水泥砂浆找平层
25×0.015=0.3KN/m
2
20×0.010=0.2KN/m220×0.02=0.4KN/m2
非组合楼盖(压型钢板-选用YX-75-230-690,上混凝土层厚80折算厚度100mm)
25×0.10=2.50KN/m2
压型钢板0.18KN/m2
总计活载:
3.58KN/m22.0KN/m2
ii:卫生间恒载:
瓷面砖150×150×810厚素水泥浆结合层一道高分子卷材一层(三毡四油)20厚1:3水泥砂浆找平层
19.8×0.008=0.1584KN/m2
20×0.010=0.2KN/m2
0.4KN/m2
20×0.02=0.4KN/m
2
非组合楼盖(压型钢板-选用YX-75-230-690,上混凝土层厚80折算厚度100mm)
25×0.10=2.50KN/m2
压型钢板总计活载:
0.18KN/m23.84KN/m22.0KN/m
2
③.墙体荷载:
内外墙采用粉煤灰轻渣空心砌块(390mm×190mm×190mm)内墙做法:
5
8.0kN/m3
文天学院2012届本科生毕业设计(论文)
5厚1:0.3:3水泥石灰膏砂浆粉面12厚1:1:6水泥石灰膏砂浆打底外墙做法:(聚苯板保温层)聚合物砂浆10mm挤塑聚苯板保温层20厚1:3水泥砂浆找平层
20×0.005=0.1KN/m2
2
20×0.012=0.24KN/m
20×0.01=0.2KN/m2
0.4
20×0.02=0.4
KN/m2KN/m2
④.查表知:
主梁自重:1.034KN/m次梁自重:0.654KN/m柱自重:2.283KN/m
2.1.4初选确定杆件截面尺寸
钢材宜采用碳素结构钢Q235,按照冲击韧性要求并且考虑到焊接,选择Q235C。梁截面形式选热轧H型钢,柱截面选焊接工字型钢。若选择H型钢,则应根据要求从H型钢产品表中确定高宽尺寸及壁厚。对于梁截面,首先应确定梁高hs,根据《钢结构规范》附录A表A.1.1挠度容许值,按表2.1.3确定出hmin,主梁的挠度容许值为[w]/l=1/400,采用Q235C钢,对应的hmin=1/15。次梁的挠度容许值为[w]/l=1/250,采用Q235C钢,对应的hmin为1/24。主梁的跨度为8000mm,次梁的跨度为7500mm,主梁高h≥8000/15=533mm,初步取主梁高为600mm。次梁高h≥7500/24=313mm,初步取次梁高为350mm。再根据简略的梁荷载、内力计算确定出截面抵抗矩WX和腹板宽度,然后查H型钢表确定型号。(1).计算确定次梁型号。
楼面活载为4.0KN/m2,假设楼板厚为100mm以及建筑层做法。次梁间距为4.0m。按次梁为简支梁计算
次梁所受荷载标准值为:活载qQ=4.0×4.0=16.0KN/m
恒载qg=25×0.10×4.0=10.0KN/m
次梁所受荷载设计值为:q=1.2qg+1.4qQ
=1.2×16.0+1.4×10.0
6
KN/m
文天学院2012届本科生毕业设计(论文)
=33.2KN/m
11
次梁所受最大弯矩M=ql2=×33.2×7.52=233.4KN•M8811
次梁所受剪力V=ql=×33.2×7.5=124.5KN22另外,假设梁自重引起的弯矩为0.02M
M≥Wrfxxx1.02×233.4×106=×10−3=1054.6cm3
1.05×215
tw≥
Vf124.5×103==2.85mmh125×350v根据以上条件选择次梁型号,梁主要受弯,因此采用窄翼缘最优。型号为:HN400×200×8×13
截面特征为:AS=83.37cm2,Ix=22775cm4,ix=16.53cm,Wx=1139cm3iy=4.56cm,Wy=173.5cm3(2).计算确定主梁型号。
楼板设计成为单向板,因此,主梁主要承受次梁传来的集中荷载。次梁间距为7500mm。主梁间距为8000mm。先按主梁为简支梁计算次梁传来的集中荷载计算:
次梁所受荷载标准值为:活载qQ=4.0×4.0=16.0KN/m
恒载qg=25×0.10×4.0=10.0KN/m
次梁所受荷载设计值为:q=1.2qg+1.4qQ
=1.2×16.0+1.4×10.0=33.2KN/m
主梁所受集中力为:p=ql1==33.2×7.5=249KN11
pl=×249×8.0=498KN•M44
次梁所受剪力V=p=249KN主梁所受最大弯矩M=
另外,假设梁自重引起的弯矩为0.02M
KN/m
Iy=1735cm4,
M≥Wrfxxx1.02×498×106
=×10−3=2250cm3
1.05×215
tw≥
Vf249×103==3.74mm125×533hv7
文天学院2012届本科生毕业设计(论文)
根据以上条件选择次梁型号,梁主要受弯,因此采用窄翼缘最优。型号为:HN600×200×11×17
截面特征为:AS=131.71cm2,Ix=73749cm4,ix=23.66cm,Wx=2458cm3Iy=2273cm4,iy=4.151cm,Wy=227.3cm3(3)计算确定柱的型号
估算柱所受的轴向荷载为:G=7.5×8.0×(1.2×3.5+1.4×4.0)
=588KN
底层柱所受轴向荷载设计值为:3G=3×588=17KN按轴心受压计算,假设长细比λ=50
根据此长细比查表可知:轴心受压柱的稳定系数ψ=0.856因此
N17×1033≥==9584.9cmAcϕf0.856×215
取lo=(1.2~1.5)H=1.35×4.5=6.08m
有等强度原理,ix=iy=lox/λ=loy/λ=6080/50=121.6mm柱截面高h=ix/α1=121.6/0.43=282.8mm柱截面宽度b=iy/α2=121.6/0.24=506.7mm
综合以上条件初步选择焊接工字型柱截面型号为:400×400×18×28截面特征值为:AS=285.92cm2Ix=93000cm4ix=17.7cmIy=31000cm4
iy=10.2cm
Wx=1530cm3
Wx=4490cm3
按照《抗震规范》8.2.5-1式初步验算以满足强柱弱梁要求。验算式为:其中:
Wpc为柱的塑性截面抵抗矩
Wpb为主梁的塑性截面抵抗矩
N为柱计算处所受轴力
主梁的塑性截面抵抗矩为:
AC为柱的截面面积
h600
Wpb=tb(h−t)+tw(−t)2=17×200×(600−17)+11×(−17)2=2863179mm3
22柱的塑性截面抵抗矩为:
h400
Wpc=tb(h−t)+tw(−t)2=28×400×(400−28)+18×(−28)2=46912mm3
22
验算强柱弱梁:
8
文天学院2012届本科生毕业设计(论文)
Wpc(f−
N)≥γxfWpbAC17×103
Wpc(210−)≥1.05×210×2863179
28592
Wpc≥4257cm3
(4)结构其它构件的确定
满足要求。
从建筑节能、防火、抗震等因素出发确定墙体材料、厚度及构造式从防火方面考虑:二级防火要求非燃烧体最大耐火极限为4小时从节能方面考虑:要防晒、隔温保热、强度高而重量低
从抗震方面考虑:要有多道防线,地震时能消耗能量,不对主体结构产生太大影响
因此,墙体材料采用加气混凝土块体材料。细部构造祥图见墙体节点构造祥图。楼梯的设计也采用钢结构形式,加混凝土保护层防火。详细情况见楼梯设计部分。
2.2结构计算简图2.2.1计算简图
结构计算简图必须先确定底层柱高取值,取值大小与基础形式、厚度、埋深等因素有关。因此,根据地质报告和场地条件先确定基础形式和埋深,分析可采用柱下基础。地表以下2m处就是稍密卵石层,其承载力较大可把基础放于上面,再加上平整场地时室外回填土要高出天然地面0.3m,因此基础埋深为1.65m。此深度大于1.5m,所以柱脚的嵌固位置取在室外地面以下1.5m处。室内外高差为0.48m,标准层高为4.5m,因此,底层柱计算高度取1.5+0.48+4.5=6.48m,其它各层柱的计算高度取层高4.5m
.1框架恒载、活载简图2.2.12.2.1.1
首先选择一榀框架做计算,考虑到手算速度和精度都不如计算机,选择④轴框架最为快捷并且误差和计算机会最小。i:作恒载计算简图
9
文天学院2012届本科生毕业设计(论文)
(4×6.44×
1
+0.66)×7.5=102KN2
恒载计算简图2-1
主梁自重相对于其它荷载比较小,因此,
把主梁自重简化为集中荷载对计算结果影响很小。求P1
次梁传到主梁上的集中力:外墙重:
1
(4×3.58×+0.66)×7.5=58.7KN2
(4.5×7.5−4×2.5)×0.19×0.8=36.1KNP1
求
=94.80KN
P1'
(4×3.58+0.66)×7.5=112.4KN次梁传到主梁上的集中力:
P1'
求P2
=112.4KN
次梁传到主梁上的集中力:外墙重:1
(4×3.58×+0.66)×7.5=58.7KN2
(4.5×7.5-4×2.5)×0.19×8.0=36.1KNP2
=94.80KN
求P2'
P2'=P1'=
求P3
112.4KN
10
文天学院2012届本科生毕业设计(论文)
次梁传到主梁上的集中力:P3=
102KN
求P'3
次梁传到主梁上的集中力:(4×6.44+0.66)×7.5=198.2KNP3'
=198.2KN
主梁自重:1.034KN/m
I:恒载作用下的简图如下:
恒载作用下的简图2-2
II:作活载计算简图
11
文天学院2012届本科生毕业设计(论文)
活载作用下的简图2-3
方法同恒载计算,主梁只有次梁传递的活载集中力。P1=4×0.5×4.0×7.5=60KNP1'=4×4×7.5=120KNP2=4×0.5×4.0×7.5=60KNP2'=4×4×7.5=120KNP3=4×0.5×0.5×7.5=7.5KNP3'=4×0.5×7.5=15KN活载简图如下:
12
文天学院2012届本科生毕业设计(论文)
.2框架水平地震作用简图2.2.12.2.1.2
1).计算各层重力荷载代表值。i:底层
①.墙和门窗重计算:外墙高为h=4.5m
外墙长=52.5×2+24×2=153m外墙宽=0.190m
外墙毛体积:153×4.5×0.19=130.82m3
内墙毛体积:5×4.5×0.19+9×4.5×0.19=11.97m3门洞口面积计算:37×2×2.5=185㎡窗洞口面积计算18×3×2.4=129.6㎡门重(选用木门)0.2KN/㎡窗重(选用钢框玻璃窗)0.5KN/㎡
重G=(130.82+11.97)×8-185×0.5-129.6×0.2=1024KN②.楼板重:
⑴.车间楼板、仓库、更衣间、门厅及辅助用房楼板楼板总宽为:24m楼板总长为:52.5m
重G=(7.58×990+7.5×16×5.58)=8174KN⑵.卫生间楼板重:8×7.5×5.84=350.4KN
⑶.楼梯间重:2×63.94=127.88KN⑷.主、次梁重和柱重主梁:8×24×1.034=198.5KN次梁:7×52.5×0.654=240.34KN柱:32×6.48×2.2834=473.5KN此层重力荷载代表值:
G1=1024+8174+350.4+127.88+198.5+240.34+473.5
13
文天学院2012届本科生毕业设计(论文)
=10562KNii:第二层①.墙和门窗重计算:外墙高为h=4.5m
外墙长=52.5×2+24×2=153m外墙宽=0.190m
外墙毛体积:153×4.5×0.19=130.82m3
内墙毛体积:5×4.5×0.19+9×4.5×0.19=11.97m3门洞口面积计算:37×2×2.5=185㎡窗洞口面积计算18×3×2.4=129.6㎡门重(选用木门)0.2KN/㎡窗重(选用钢框玻璃窗)0.5KN/㎡
重G=(130.82+11.97)×8-185×0.5-129.6×0.2=1024KN②.楼板重:
⑴.车间楼板、仓库、更衣间、门厅及辅助用房楼板楼板总宽为:24m楼板总长为:52.5m
重G=(7.58×990+7.5×16×5.58)=8174KN⑵.卫生间楼板重:8×7.5×5.84=350.4KN
⑶.楼梯间重:2×63.94=127.88KN⑷.主、次梁重和柱重主梁:8×24×1.034=198.5KN次梁:7×52.5×0.654=240.34KN柱:32×4.5×2.2834=328.8KN此层重力荷载代表值:
G2=1024+8174+350.4+127.88+198.5+240.34+328.8=10417.3KNiii:第三层
14
文天学院2012届本科生毕业设计(论文)
①.墙和门窗重计算:外墙高为h=4.5m
外墙长=52.5×2+24×2=153m外墙宽=0.190m
外墙毛体积:153×4.5×0.19=130.82m3内墙毛体积:5×4.5×0.19+9×4.5×0.19=11.97m3
门洞口面积计算:37×2×2.5=185㎡窗洞口面积计算18×3×2.4=129.6㎡门重(选用木门)0.2KN/㎡窗重(选用钢框玻璃窗)0.5KN/㎡
重G=(130.82+11.97)×8-185×0.5-129.6×0.2=1024KN②.屋面板重楼板总宽为:24m楼板总长为:52.5m
重G=6.440KN/m2×24×52.5=8114.4KN主、次梁重和柱重
主梁:8×24×1.034=198.5KN次梁:7×52.5×0.654=240.34KN柱:0.5×32×4.5×2.2834=1.4KN
重G3=1024+8114.4+198.5+240.34+1.4=9741.KN重力荷载代表值简图如下:2).计算结构自振周期采用顶点位移法计算①.计算框架的抗剪刚度Cf
采用非组合楼盖,楼板对梁截面无加强作用,不考虑板的影响。钢的弹性模量为206×103N/mm2
2.2.3各层重力荷载代表值(KN)
15
文天学院2012届本科生毕业设计(论文)
主梁的线刚度
类别
材料
截面
跨度截面惯性矩(m)(×10-4m4)
线
刚
度
Kb=
EI(×104KN•m)l框架梁Q235B
HN600×200×11×17
8.07.371.
柱的线刚度
层号
材料
截面
层高
截面惯性矩I(×10-4m4)
线刚度
Kc=
2~3
Q235B
400×400×18×28
4.50
9.3
EI(×104KN•m)l4.39
1Q235B400×400×18×286.4.32.96
求各柱的抗侧刚度D值:首先求梁柱的线刚度比k,
D值修正系数α一般层
16
文天学院2012届本科生毕业设计(论文)
k=
k1+k2+k2+k4
2kck2+kk=
k2+k42kck2+kα=
底层
α=
k=
k2kc0.5+k2+k各柱刚度计算
k=
k1+k2
kc0.5+k2+kα=
α=
D=α•
边柱底层2~3层
kα0.430.177
12Kc(×104KN/m)2
h0.0.43
0.3650.460
α中柱底层2~3层
kD=α•
12Kc(×104KN/m)2h1.280.86
0.540.30
0.4570.780
底层柱:
∑D=(3650+4570)×16=131520KN/m2、3层柱:∑D=(4600+7800)×16=198400KN/m框架自振周期计算:
17
文天学院2012届本科生毕业设计(论文)
基本周期
T1的计算
G层
(KN)
i∑Di∑Gini位
(KN/m)∑Gi∆ui=
∑Diui=∑∆uii=1
iGiuiGiui2
(KN)(m)
30720.920158.99741.
0.2330.1020.049
(m)
0.2330.3350.384
•m)(KN•m)(KN2
123
1056210417.39741.
131520198400198400
2355.334.83740.8
548.81169.11436.5
取Ψ=0.5
TT=2ΨT∑Guiu=1nii=1n2i=2×0.5i∑Gu2101.4=0.47s9585.93).采用底部剪力法求地震作用由设计资料知:
场地设防烈度为7度,设计基本地震加速度为0.10g,设计地震分组为第二组,场地类别为Ⅱ类场地。依据以上条件查表:
多遇地震时水平地震影响系数最大值为αmax=0.08,特征周期值Tg=0.4s,钢结构阻尼比为:ζ所以
=0.035考虑多遇地震
γ=0.9+
0.05−ζ0.05−0.035
=0.9+=0.921
0.5+6ζ0.5+6×0.0350.05−ζ0.05−0.035
=0.02+=0.023
4+32ζ4+32×0.035
η1=0.02+
18
文天学院2012届本科生毕业设计(论文)
0.05−ζ0.05−0.035
η2=1+=1+=1.11
0.08+1.6ζ0.08+1.6×0.035
其中:γ为曲线下降段衰减指数,
η1为直线下降段的下降斜率调整系数,η2为阻尼调整系数,
因为Tg γ0.40.921 =()×1.11×0.08=0.0770.47 结构等效总重力荷为: Geq=c∑Gi=0.85×(9741.6+10417.3+10562)=26112.8KNi=1 3 结构底部总剪力为: FEK=α1Geq=0.077×26112.8=1998.8KN所以不考虑顶部附加地震作用 Fi= GiHi∑GHjj=1 nFEKj其中:Gi--各层重力荷载代表值 Hi--第i层离计算最低点的距离 楼层水平地震作用 Gi(KN) 层号321 9741.610417.3105623072.1 Hi(m) 15.4810.986.48 GIHi(KN•m) 150799.97114381.9568441.76333623.68 Fi(KN) 903.5685.3410.0 ∑ 4).计算框架的水平地震作用 19 文天学院2012届本科生毕业设计(论文) 质点i水平地震作用标准值、楼层地震剪力及;楼层层间位移的计算过程参见下表: 图2.2.4水平地震作用计算简图图2.2.5水平地震作用下剪力 Fi、Vi和∆ue的计算 HiGiHi∑GiHiFiGi2.2.4图水平地震作用下计算简层(KN)9741.610417.310562(KN)(KN)Vi∑Di∆ue(KN)(KN/m)(m)32115.4810.986.4815080011438268442333624903.5685.3410903.51519991984001984001315200.0050.0080.015横向水平地震作用下内力可由手算求出,通过底部剪力法计算求得 20 文天学院2012届本科生毕业设计(论文) 水平地震作用下计算简图2.26 柱层h(m) Vi DN/m)(KN)(KN/m)(K∑DD∑DVik(KN) ky0 M上 (KN/m)(KN/m) M下 3边 2柱 1 4.5903.519840046000.02320.780.430.328.0565.46 4.51588.819840046000.02336.540.430.582.2282.22 6.481998.813152036500.02855.970.0.7253.88108.81 3中 2柱 1 4.5903.519840078000.03935.240.860.3860.2698.32 4.51588.819840078000.03961.960.860.45125.47153.35 6.481998.813152045700.03561.961.280.61276.53176.80 AB跨梁端剪力 层 BC跨梁端剪力柱轴力 l(m) M左M右 M+MV=左右 ll(m) M左 M右 V=M左+M右边柱 Nl中柱 N38.065.49.1614.338.049.19.1612.2914.332.04 28.0110.27106.8127.148.0106.8106.826.741.472.48 21 文天学院2012届本科生毕业设计(论文) 18.0191.03125.4739.568.0151.1151.137.881.034.24 水平地震作用柱端剪力和柱弯矩标准值水平地震作用下框架梁剪力和柱端轴力标准值 验算框架层间弹性位移:首层: ∆ue0.01511 == 二层:(满足要求) 三层:(满足要求) 验算框架柱顶侧移:(满足要求) 横向水平地震作用下N/V图横向水平地震作用下M图 .3框架风载作用简图2.2.12.2.1.3 风荷载工况有左、右风之分,一般作出左风风载简图。风载对于钢框架-支撑结构和地震一样也要考虑协同工作。 22 文天学院2012届本科生毕业设计(论文) 风载体形系数µs迎风面和背风面力的方向相同,因此,可以把两者合算。 µs=0.8+0.5=1.3 风振系数βzβz=1+ϕz基本风压B类粗糙度 ξνµzϖ0=0.4KN/m2 T1=0.47s, ϖ0T12=0.4×0.472=0.088 查规范,B类地区,知脉动增大系数,ξ=1.47 H15.48==0.5B24 查规范知脉动影响系数,ν=0.42结构总高度为:15.48m, wz=βzµzBµsw0=(1+ϕz风压单位高度上的 ξν)µBµw=(µz+ϕzξν)Bµsw0µzzs0 =(µz+ϕz×1.47×0.42)×24.0×1.3×0.4=(µz+ϕz×0.617)×12.48KN/m对于质量和刚度沿着高度均匀分布的房屋,结构振型系数可以取 ϕz= zz= H15.48 离地面高度z(m) 23 各分段高度处风荷载值列表计算层数 ϕzµzϕz×0.617µz+ϕz×0.617 Wz(KN/m)文天学院2012届本科生毕业设计(论文) 123 6.4810.9815.48 0.420.711 1.01.031.15 0.260.440.617 1.261.471.767 15.7218.3522.05 风荷载作用下计算简图 风荷载水平作用下内力可由力学求解器算出 风载作用下计算简图风载作用下M图 风载作用下V图 风载作用下内力计算 杆端内力值 风载作用下N图 (乘子=1)---------------------------------------------------------------------------------------------- 24 文天学院2012届本科生毕业设计(论文) 杆端1 ----------------------------------------单元码 轴力 剪力 弯矩 杆端2 ------------------------------------------轴力 剪力 弯矩 25 文天学院2012届本科生毕业设计(论文) 118.2173228.4500344932.135151954-17.48437505-10.73974606-10.96826177-4.638183598-3.3733629-9.6632949010-19.506676111-16.322998012-9.36316013-1.9792480514-9.3563232415-7.8238525416-6.37658691170.0373162518-0.7011460119-2.279262201.20095766211.9144426622 3.49682878 12.82406786.460343094.43340920-3.034013-2.73928438-1.59961342-3.140123754.471239006.4504031412.8269244-6.31488254-5.572028-6.290527-9.83913878-8.26099517-9.843381296.7473047313.70615.23873076.3975314013.781961615.2294079 -50.9519544-9.320692-6.4535041613.49683729.005038-1.3321770711.4723715-13.6815878-19.7119420-32.160345626.204151122.3456724.168312441.4602233.035825037.2718325-20.4471998-33.9785192-42.57934-19.2118140-34.2339330-42.5390743 26 18.217328.450034492.13515195-17.4843750-10.7397460-10.9682617-4.63818359-3.373362-9.66329490-19.5066761-16.3229980-9.363160-1.97924805-9.35632324-7.82385254-6.376586910.03731625-0.70114601-2.2792621.200957661.914442663.49682878 12.82406786.460343094.43340920-3.034013-2.73928438-1.59961342-3.140123754.471239006.4504031412.8269244-6.31488254-5.572028-6.290527-9.83913878-8.26099517-9.843381296.7473047313.70615.23873076.3975314013.781961615.2294079 32.148005219.7506913.4968372-10.8071494-1.33217707-7.73944254-13.68158786.4387709.3148720750.9581245-24.3149091-22.2656857-26.1509297-37.2442080-33.0521362-41.475217712.682066327.700684156.167626212.200065127.7844556.14748 文天学院2012届本科生毕业设计(论文) 2.3.内力计算 2.3.1框架在竖向力作用下的内力计算 首先进行弯矩计算,然后在通过杆件和节点平衡计算剪力和轴力。弯矩分配采用弯矩二次分配法计算, .1框架在竖向力恒载作用下的内力计算2.3.12.3.1.1 求各杆件的弯矩分配系数kb=1.×104KN·m kc底=2.96×104KN·m kc标准=4.39×104KN·m m公式如下:梁端弯矩分配系数:µb= kbi∑ki=1 n, bi+∑kcjj=1 柱端弯矩分配系数:µc= kcj∑ki=1 nbi+∑kcjj=1 m其中:n—节点处梁总数m—节点处柱总数; 恒载作用下计算简图 恒载作用下由结构力学求解器得出内力图 27 文天学院2012届本科生毕业设计(论文) 恒载作用下N图恒载作用下V图 恒载作用下M图 28 文天学院2012届本科生毕业设计(论文) µ=0.4µ=0.6µ=0.41µ=0.35µ=0.15µ=0.23µ=0.54µ=0.23µ=0.15µ=0.35µ=0.18µ=0.17µ=0.39µ=0.17µ=0.27µ=0.41µ=0.48µ=0.20µ=0.32钢框架结构分配系数简图恒载作用下内力计算 杆端内力值 (乘子=1) --------------------------------------------------------------------------------------------杆端1 ----------------------------------------单元码 轴力 剪力 弯矩 杆端2 ------------------------------------------轴力 剪力 弯矩 --------------------------------------------------------------------------------------------123456710 -501.688446-351.304297-197.288777-53.4654998-59.9327621-59.9327468-53.4654998-197.288777-351.304299-501.688449 -8.24538278-19.7002954-48.652121592.6737290100.231704-96.0900088113.809128.652123019.70029668.24538446 17.810025155.196884079.2762723-139.658274-205.870004187.314159-224.310818-139.658278-33.4544483-35.6200592 29 -501.688446-351.304297-197.288777-53.4654998-59.9327621-59.9327468-53.4654998-197.288777-351.304299-501.688449 -8.24538278-19.7002954-48.6521215-113.80912796.0900081-100.231704-92.673729948.652123019.70029668.24538446 -35.6200552-33.4544455-139.658274-224.310821187.314159-205.870007-139.65827879.276275455.196886517.8100320 文天学院2012届本科生毕业设计(论文) 111213141516171819202122 28.951826025.467551528.9518211.454912611.3160711.4549121-412.359442-6.551921-884.375772-412.359441-6.551920-884.375770 59.215520260.335999361.4578355.584148860.335999365.087849.625110781.140836291.00281434-4.625108-1.14083376-1.00281230 -112.730717-117.122721-121.694550-90.8169392-119.669186-128.831742-18.4408166-0.30335741-4.3321563018.44081080.303351634.33215077 28.951826025.467551528.9518211.454912611.3160711.4549121-412.359442-6.551921-884.375772-412.359441-6.551920-884.375770 -61.45798-60.3360006-59.2155216-65.0878511-60.3360006-55.58415044.625110781.140836291.00281434-4.625108-1.14083376-1.00281230 -121.694556-117.122726-112.730723-128.831748-119.669191-90.81694574.2684772.830405872.16608061-4.268472-4.83040028-2.16607292 -------------------------------------------------------------------------------------------- .2框架在竖向力活载作用下的内力计算:2.3.12.3.1.2 活载作用下的内力计算简图活载作用下N图 30 文天学院2012届本科生毕业设计(论文) 活载作用下V图 活载作用下内力计算 杆端内力值 (乘子=1) 活载作用下M图 --------------------------------------------------------------------------------------------杆端1 ----------------------------------------单元码 轴力 剪力 弯矩 杆端2 ------------------------------------------轴力 剪力 弯矩 --------------------------------------------------------------------------------------------1234567101112 -247.7260-132.199161-15.9326806-12.5294628-12.6112422-12.6112413-12.5294623-15.9326806-132.199161-247.7260-15.8558281-13.9214756 -7.25320510-27.9695597-12.11373167.801612936.84823862-6.848238617.1983870912.113731527.96955977.2532050556.2680960.0000000 15.6680711.507218537.7724739-16.7393182-13.6028213.8242511-14.3232481-16.7393181-61.3558003-31.3326977-99.1282743-120.959624 31 -247.7260-132.199161-15.9326806-12.5294628-12.6112422-12.6112413-12.5294623-15.9326806-132.199161-247.7260-15.8558281-13.9214756 -7.25320510-27.9695597-12.1137316-7.198387076.84823862-6.84823861-7.8016129112.113731527.96955977.25320505-63.7335190-59.9999999 -31.3326978-61.3558004-16.7393182-14.323248013.8242511-13.60281-16.739318137.7724738.507218515.6680710-128.9926-120.959624 文天学院2012届本科生毕业设计(论文) 13141516171819202122 -15.855828120.716354618.830420520.7163546-29.0476588-272.781177-517.083078-29.0476588-272.781177-517.083078 63.733519055.698099060.0000000.30190100.6614852.580967420.69503334-0.661491-2.58096749-0.69503339 -128.9926-95.83991-121.216611-130.255124-0.71681985-5.57874340-3.002902810.716820005.578743543.00290295 -15.855828120.716354618.830420520.7163546-29.0476588-272.781177-517.083078-29.0476588-272.781177-517.083078 -56.26809-.3019010-59.9999999-55.698090.6614852.580967420.69503334-0.661491-2.58096749-0.69503339 -99.1282741-130.255124-121.216611-95.83991622.458059096.035610001.50091321-2.45805921-6.03561014-1.50091340 -------------------------------------------------------------------------------------------- 2.4.内力组合 在进行荷载组合时,应该考虑活载的最不利布置。对多层框架,如果考虑地震组合,可以不考虑活载的不利布置;如果不考虑地震组合,可将活载下的内力乘以1.1~1.2的放大系数。由于本工程位于7度抗震设防区,在设计时不考虑地震作用,因此组合时将活载乘以1.15的放大系数。 对多层框架,根据《建筑结构荷载规范》(GB50009)的规定,对梁和柱的计算都要考虑活载的折减。本建筑在设计楼面梁时,主梁的从属面积超过25m2,活载乘以0.9的折减系数;设计柱时,按《建筑结构荷载规范》(GB50009)中表4.1.2进行活载折减。 本建筑的荷载组合采用《建筑结构荷载规范》(GB50009)3.2.4的一般排架、框架结构的基本组合简化规则,由可变荷载效应控制的组合: ①1.2SGk+1.4SW;②1.2SGk+1.4SQ;③ 1.2SGk+0.9×1.4×(SW+SQ) ; ④1.2×(SGK+0.5×SQ)+1.3SE32 文天学院2012届本科生毕业设计(论文) 由永久荷载效应控制的组合:1.35SGk+1.4×0.7×SQ+1.4×0.6×SW。 梁内力组合2.4.1框架框架梁 因为各层梁截面均相同,而顶层荷载较标准层大,故只取首层、顶层的边跨梁和中间梁组合。框架梁内力组合见表2.4.2 33 文天学院2012届本科生毕业设计(论文)截面内力 ①活荷载 ②-31.33-7.25-247.15.66-7.25-247.-61.35-27.96-132.19.50-27.96-132.19-16.73-12.11-15.9337.77-12.11-15.931.500.69-517.10-3.000.69-517.106.032.58-272.78-5.572.58-272.782.450.-29.04-0.720.-29.04左风荷载 ③32.1412.8218.28-50.9512.8218.2819.756.468.45-9.326.468.4513.494.432.13-6.454.432.1356.1615.24-2.27-42.5715.23-2.2827.7013.71-0.70-33.9813.71-0.7012.686.740.04-20.456.750.04左地震荷载④-32.14-12.82-18.2850.95-12.82-18.28-19.75-6.46-8.459.32-6.46-8.45-13.49-4.43-2.136.46-4.43-2.13-56.16-15.242.2742.57-15.232.28-27.70-13.710.7033.98-13.710.70-12.68-6.74-0.0420.45-6.75-0.04-2.48-125.47-2.48.32-2.04-60.26-2.042.48125.472.48-98.322.0460.262.04-4.24153.354.24-153.35-4.24-276.534.24276.53-81.0382.2241.47-82.2241.4765.46-14.33-28.05-14.33176.8081.03-82.22-41.4782.22-41.47-65.4614.3328.0514.33-176.80-81.03-253.8881.03253.88⑤191.03⑥-191.03右地震荷载1.2恒+1.4活1.2×①+1.4×②-86.58-20.04-948.9743.28-20.04-948.97-126.03-62.78-606.63156.53-62.78-606.63-191.00-75.33-258.94148.00-75.33-259.044.692.17-1785.10-9.402.17-1785.1814.244.98-1157.75-8.1.98393.978.546.44-535.48-23.146.44-535.481.2×①+1.4×③或④→2.288.06-576.33-49.978.06-576.33-12.49-14.60-409.7353.18-14.60-409.73-148.69-52.18-233.6686.09-52.18-233.7581.2222.54########-.7922.52########44.5820.56-776.84-47.9320.56774.8822.8614.98-494.76-50.7614.99-494.76←-87.72-27.84-627.5192.69-27.84-627.51-67.79-32.68-433.3979.28-32.68-433.39-186.47-.58-239.62104.17-.58-239.72-76.03-20.14-1057.9854.40-20.12-1058.05-32.98-17.83-774.8847.21-17.83776.84-12.-3.-494.886.50-3.91-494.881.2恒+0.9×1.4(活+风)1.2×①+0.9×1.4×(②+③或④)→←-41.70-122.69-2.87-1.23-23.11-2.87-1.23-92.56-50.73-577.47135.75-50.73-577.47-171.66-68.06-254.03134.59-68.06-254.1275.2421.27-1715.57-62.6121.26-1715.68.3021.-1120.44-50.1921.431.2824.1814.84-531.36-48.8014.86-531.36-35.18-937.29105.29-35.18-937.29-142.33-67.01-598.77159.24-67.01-598.77-205.66-79.22-259.40150.85-79.22-259.49-66.28-17.13-1709.8544.66-17.12-1709.92-21.51-12.66-1118.6835.44-12.633.04-7.78-2.14-531.462.73-2.15-531.461.35恒+0.7×1.4活+0.6×1.4风1.35×①+0.7×1.4×②+0.6×1.4×③或④→←-51.77-105.76-7.46-904.74-3.42-7.46-904.74-88.69-48.57-596.70129.-48.57-596.70-193.59-73.82-280.04138.61-73.82-280.1551.5614.83-1702.47-44.5414.82-1702.5735.7015.58-1140.75-34.4115.58604.9318.8012.53-585.10-42.7812.53-585.10-29.00-935.4582.17-29.00-935.45-121.87-59.42-610.90145.55-59.42-610.90-216.25-81.27-283.62149.46-81.27-283.73-42.79-10.78-1698.6626.97-10.77-1698.74-10.84-7.45-1139.5822.68-7.45606.11-2.501.20-585.17-8.421.19-585.171.2*(恒+0.5*活)+1.3S震1.2*(①+0.5×②)+1.3×⑤或⑥→←186.82-309.86-14.24-855.99-299.29-14.24-855.9929.94-40.42-446.96-1.96-40.42-446.96-92.52-65.65-2.8381.32-65.65-2.92233.331.61-1376.93-366.491.61-1377.02208.772.92-942.75-166.812.92608.97134.405.93-514.90-100.905.93-514.90-14.24-5.32360.80-14.24-5.32-183.84-40.42-554.79211.81-40.42-554.79-262.72-65.65-227.57154.25-65.65-227.67-226.351.61-1365.91352.491.61-1365.99-1.942.92-936.30159.412.92615.42-121.235.93-509.5955.785.93-509.595-1上M/kN⋅m-35.60V/kN-8.24N/kN-501.60M/kN⋅m17.80-309.86-14.24-5.32360.80-14.24-5.32-183.84-40.42-554.79211.81-40.42-554.79-262.72-65.65-227.57154.25-65.65-227.67233.331.61-1365.91-366.491.61-1377.02208.772.92-936.30-166.812.92608.97134.405.93-514.90-100.905.93-514.90-86.58-20.04-948.9743.28-20.04-948.97-948.97-62.78-606.63156.53-62.78-606.63-216.25-81.27-283.62149.46-81.27-283.734.692.17-1785.10-9.402.17-1785.1814.244.98-1157.7547.21-17.83776.84-2.501.20-585.17-8.421.19-585.17下上V/kN-8.24N/kN-501.60M/kN⋅m-33.45V/kN-19.70N/kN-351.30M/kN⋅m9-5下V/kN55.19-19.70N/kN-351.30M/kN⋅m-139.65上V/kNN/kN-48.65-197.2079.27M/kN⋅m下13-9上V/kN-48.65N/kN-197.28M/kN⋅m2.16V/kN1.00N/kN下M/kN⋅mV/kN-884.30-4.331.00-884.37M/kN⋅m4.83上N/kN6-2下上V/kN1.14N/kN-6.55M/kN⋅m-0.30V/kN1.14N/kN6.55M/kN⋅m4.26V/kN4.62N/kN-412.35-18.444.62-412.35M/kN⋅m下弯矩以使柱顺时针转为正,轴力以拉力为负、压力为正,剪力以使柱顺时针转为正、逆时针转为负34 文天学院2012届本科生毕业设计(论文) 面内力恒荷载 ①-90.8111.4555.58-128.8311.45-65.08123.25-112.7328.9559.21-121.6928.95-61.45115.86-139.66-53.4692.67-224.31-53.46-113.80223.23-119.6611.3160.33-119.6611.31-60.33113.40-117.1225.4660.33-117.1225.46-60.33115.95-205.87-59.93100.23 187.31-59.93 96.09187.31活荷载 ②-95.8320.7155.69-130.2520.71-.30126.95 -99.1-15.8556.26-128.99-15.85-63.73125.94-16.73-12.527.80-14.32-12.52-7.2014.51-121.2018.8360.00-121.2018.8360.00118.78-120.95-13.9260.00-120.95-13.9260.00119.04-13.6 -12.61 6.8413.82 -12.61 6.8413.8233.03-7.82-8.26-33.05-7.82-8.2622.35-9.36-5.57-22.27-9.36-5.57 9.-10.73-2.73-1.33-10.73-2.73-33.037.828.2633.057.828.26-22.359.365.5722.279.365.57-9.10.732.731.3310.732.73151.1437.80151.1437.80106.8126.70106.8126.7049.1612.2949.1612.29-151.1413.49-17.48-3.03-10.8-17.48-3.03-13.4917.483.0310.817.483.0365.4614.3349.1614.33-65.46-14.33-49.16-14.3326.2-16.32-6.31-24.31-16.32-6.31-26.216.326.3124.3116.326.31110.2727.14106.8127.14-110.27-27.14-106.81-27.14 ③41.46-9.35-9.83-37.24-9.35-9.83右风荷载④-41.469.359.8337.249.359.83左地震荷载⑤191.0339.56151.1439.56右地震荷载⑥-191.03-39.56-151.14-39.561.2恒+1.4活1.2×①+1.4×②-243.1342.73144.66-336.9542.73-168.12325.63#VALUE!12.55149.82-326.6112.55-162.96315.35-191.01-81.68122.12-2.22-81.68-146.288.19-313.2739.93156.40-313.2739.9311.60302.37-309.8711.06156.40-309.8711.0611.60305.80-266.08#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!244.121.2×①+1.4×③或④→-50.930.6552.93-206.730.65-91.86147.90-98.6011.62.22-180.0611.-82.57139.03-148.71-88.62106.96-284.29-88.62-140.80267.88-97.352.6260.83-1.862.62-83.96136.08-109.2517.45.60-171.7217.45-80.19139.14#VALUE!-86.94116.45#VALUE!-86.94#VALUE!224.77←-167.0226.8380.46-102.4626.83-.33147.90-171.9657.5979.-111.9957.59-.91139.03-186.48-39.68115.45-254.05-39.68-132.32267.88-1.8324.5283.96-97.3224.52-60.83136.08-171.8343.6680.19-109.3743.66-.60139.14-260.54-56.124.10#VALUE!-56.#VALUE!224.771.2恒+0.9×1.4(活+风)1.2×①+0.9×1.4×(②+③或④)→-177.4828.05124.48-365.6328.05-171.50307.86#VALUE!-5.79133.99-339.19-5.79-161.99297.72-171.67-101.95117.21-300.82-101.95-149.45286.16-254.6927.44137.59-337.9527.44-7.20285.74-2.781.22140.98-321.001.22-3.812.13#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!242.19←-281.9651.62149.25-271.7951.62-146.73307.86#VALUE!35.33149.-277.9235.33-146.09297.72-205.67-57.90124.85-273.61-57.90-141.81286.16-337.9247.15158.40-254.67.1513.61285.74-321.1024.81155.01-2.8824.8110.222.13-276.33#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!242.191.35恒+0.7×1.4活+0.6×1.4风1.35×①+0.7×1.4×②+0.6×1.4×③或④→←-181.68-251.3327.90121.35-332.8527.90-159.13290.80#VALUE!9.84129.77-311.119.84-150.71279.83-193.60-99.12130.20-325.92-99.12-163.23315.58-252.5727.15133.31-308.0827.15-29.58269.49-257.8712.87135.57-295.3512.87-27.32273.19#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!266.4143.61137.87-270.2843.61-142.61290.80#VALUE!37.26140.37-270.2737.26-140.11279.83-216.27-69.76135.29-307.78-69.76-158.14315.58-308.00.29147.18-252.50.29-15.71269.49-295.4228.59144.92-257.9428.59-17.97273.19-299.35#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!266.411.2*(恒+0.5*活)+1.3S震1.2*(①+0.5×②)+1.3×⑤或⑥→←81.87-414.8126.17151.54-36.2626.17-65.25224.07#VALUE!25.23140.09-84.5725.23-76.70214.60-92.53-71.66134.51-213.86-71.66-122.25276.58-19.8324.87157.54-19.8324.8712.74207.35-74.2622.20143.11-74.2622.20-1.69210.56-191.30#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!233.0626.1748.68-429.2326.17-168.10224.07#VALUE!25.2369.53-362.2825.23-147.26214.60-262.73-71.6697.26-341.67-71.66-159.51276.58-412.7924.87108.40-412.7924.87-85.54207.35-351.9722.2073.69-351.9722.20-71.11210.56-319.11#VALUE!#VALUE!#VALUE!#VALUE!#VALUE!233.06A1B1A1B1B1A1跨中M/kN⋅mN/kNV/kNM/kN⋅mN/kNV/kNM/kN⋅mM/kN⋅m-414.8126.1748.68-429.2326.17-168.10325.63-338.0925.2369.53-362.2825.23-147.26315.35-262.73-71.6697.26-341.67-71.66-159.51315.58-412.7924.87108.40-412.7924.87-85.54302.37-351.9722.2073.69-351.9722.20-71.11305.80-319.11-79.48108.40296.97-79.48103.44266.41-281.9651.62149.25-365.6328.05-171.50A2B2A2B2跨中N/kNV/kNM/kN⋅mN/kNV/kNM/kN⋅m-293.1535.33149.-326.6112.55-162.96-216.27-69.76135.51-325.92-99.12-163.23-337.9247.15158.40-412.7924.87-85.54-309.8711.06156.40-171.7217.45-80.19-299.35-84.25144.31267.97-84.25138.72B2A2M/kN⋅mN/kNV/kNM/kN⋅mN/kNV/kN跨中A3B3M/kN⋅mM/kN⋅mN/kNV/kNM/kN⋅m-151.14-37.80-106.81-26.70-106.81-26.70-49.16-12.29-49.16-12.29N/kNA3B3B3A3V/kN跨中M/kN⋅mM/kN⋅mN/kNV/kNM/kN⋅mN/kNV/kNM/kN⋅mB1C1跨中BCCB跨中BC35 BCCB文天学院2012届本科生毕业设计(论文) 柱内力组合2.4.2框架框架柱 因为各层柱子的截面相同,故只取首层、中间标准层的边柱和中柱进行内力组合。框架柱的内力组合见表2.4.1 对表2.4.1的注释:弯矩M以柱外侧受拉为正,内侧受拉为负;剪力V以使柱顺时针转为正,逆时针为负;轴力N以压力为正,拉力为负。 对表2.4.2的注释:弯矩M以梁上部受拉为正,下部受拉为负;剪力V以使梁顺时针转为正,逆时针转为负;轴力N以压力为正,拉力为负。 2.5结构、构件截面验算2.5.1框架柱截面验算 框架柱的验算包括强度、整体稳定和局部稳定验算。计算时不考虑抗震设防要求,按照《钢结构设计规范》GB50017计算。2.5.1柱5−1(1) 截面特性 柱5−1的截面为焊接工字截面,其截面特性400×400×18×28截面特征值为:AS=285.92cm2Ix=93000cm4ix=17.7cmIy=31000cm4 iy=10.2cm Wx=1530cm3 Wx=4490cm3 此压弯构件受压翼缘自由外伸宽度b1与其厚度t之比(b,1/t)即b1/t= 0.5×(400−18)235235=6.82<13=13=13,所以查表得γx=1.05。 28fy235(2)控制内力 根据内力组合表,强度验算可能由以下组合控制 ⎧Mu=−309.86kN⋅m,Md=360.86kN⋅m⎧Mu=−86.58kN⋅m,Md=43.28kN⋅m⎪⎪N=−5.32kN,N=−5.32kN⎨u⎨Nu=−948.97kN,Nd=−948.97kNd⎪V=−14.24kN,V=−14.24kN⎪V=−20.04kN,V=−20.04kN⎩ud⎩ud36 文天学院2012届本科生毕业设计(论文) (3)强度验算 截面无削弱,对第一组内力: NdMd5.32×103360.86×106 +=+=99.11Nmm2 AnγxWx285.92×101.05×4490×10满足要求。对第二组内力: NdMd948.97×10386.58×10622 满足+=+=51.55Nmm 弯矩作用平面内的稳定验算 根据《钢结构设计规范》GB50017,按有侧移框架柱计算。由于横梁A1B1的轴力很小,在计算柱长度系数时不考虑其影响。柱脚在横向为刚接,不考虑梁的组合效应,按纯钢梁计。 梁A1B1的截面为HN600×200×11×17其惯性矩为Ix=737490cm4。 K1=∑Iblbc∑Ilc= 737490800 =2.63, 93000450+930008 K2=10, 由《钢结构设计规范》附表3-1得则λx= µx=0.61, lox0.61×8==16.6<120235fy=120235235=120,ix23.66 由 b=400/400=1.00>0.8,查《钢结构设计规范》附录C此柱截面为b类h截面,查得ϕx=0.980,框架为有侧移纯框架,βmx=1.0。 π2EA3.142×2.06×105×285.92×102 N===191585.3kN,22 1.1λx1.1×16.6 ' Ex对于第一组内力: 37 文天学院2012届本科生毕业设计(论文) NdβmxMd5.32×1031.0×309.86×106 +=+ 5.32ϕxAγW(1−0.8Nd)0.980×285.92×1021.05×4490×103×(1-0.8×)xx' 191585.3NEx=88.93Nmm2 +=+ ϕxAγW(1−0.8Nd)0.980×285.92×1021.05×4490×103×(1−0.8×5.32)xx' 191585.3NEx=99.77Nmm2 纵向框架梁截面为HN400×200×8×13其惯性矩为Ix=22775cm4与柱刚接。柱脚在纵向也取刚接。K1= ∑I∑Ibcylb2×22775750==0.52,K2=10,由《钢lc310008+31000450 结构设计规范》附表3-1 µy=0.683,则λy= 0.683×8 =43.39<120235fy=120235235=120, 10.2 由《钢结构设计规范》附录C按b类截面查得 ϕy=0.882, 43.392235 ϕb=1.07−⋅=1.07−×=1.03>1,取ϕb=1.0 4400023544000235框架为有侧移纯框架,βtx=1.0。截面影响系数η=1.0。对于第一组内力: λy2fyNdβtxMd5.32×1031.0×360.80×1062 +η=+1.0×=105.94NmmϕyAϕbWx0.882×285.92×1021.0×4490×103 +η=+1.0×=47.27NmmϕyAϕbWx0.882×285.92×1021.0×4490×103 文天学院2012届本科生毕业设计(论文) 满足要求。(6)1) 局部稳定翼缘板的宽厚比 b1191235==6.82<13=13,满足要求。t282352) 腹板的高厚比 对于第一组内力: σmaxσmin NdMdy15.32×103360.8×106×1862 =+=+=94.73NmmAIx285.92×10293000×104NdMdy15.32×103360.8×106×186=−=−=−49.59Nmm2 24 AIx285.92×1093000×10 应力梯度:α0=(σmax−σmin)/σmax=⎡⎣94.73−(−49.59)⎤⎦)/94.73=1.52<1.6腹板的允许高厚比: ⎡h0⎤235235=(16α+0.5λ+25)=(16×1.52+0.5×16.6+25)=57.68⎢⎥0xfy235⎣tw⎦高厚比 h0372 ==20.67<57.68,满足要求。tw18 对于第二组内力: σmaxσmin NdMdy1948.97×10343.28×106×186=+=+=41.85Nmm2 24 AIx285.92×1093000×10NdMdy1948.97×10343.28×106×1862=−=−=24.53NmmAIx285.92×10293000×104 应力梯度:α0=(σmax−σmin)/σmax=(41.85−24.53)/41.85=0.41<1.6板的允许高厚比: ⎡h0⎤235235=(16α+0.5λ+25)=(16×0.41+0.5×16.6+25)=39.9⎢⎥0xfy235⎣tw⎦高厚比 h0372 ==20.67<39.9,满足要求。因柱均采用同一截面形式,其它柱段tw18 的局稳可不用再计算。2.5.1.2 柱9-5 39 文天学院2012届本科生毕业设计(论文) (1)截面特性 与柱5−1相同,其截面特性400×400×18×28,截面特征值为:AS=285.92cmIx=93000cm4ix=17.7cm Wx=4490cm3Iy=31000cm4 iy=10.2cm Wx=1530cm3 2 此压弯构件受压翼缘自由外伸宽度b1与其厚度t之比(b,1/t)即b1/t= 0.5×(400−18)235235=6.82<13=13=13,所以查表得γx=1.05。 28fy235(2)控制内力 根据内力组合表,强度验算可能由以下组合控制⎧Mu=−183.84kN⋅m,Md=211.81kN⋅m⎪ ⎨Nu=−554.79kN,Nd=−554.79kN⎪V=−40.42kN,V=−40.42kN⎩ud(3)强度验算 截面无削弱,对第一组内力: ⎧Mu=−948.97kN⋅m,Md=156.53kN⋅m⎪ ⎨Nu=−606.63kN,Nd=−606.63kN⎪V=−62.78kN,V=−62.78kN⎩udNdMd554.79×103211.81×106 +=+=.33Nmm2 NuMu554.79×103948.97×106 +=+=220.1Nmm2≈f=215Nmm2,工程23AnγxWx285.92×101.05×4490×10上误差在5%范围内可认为满足要求。(4) 弯矩作用平面内的稳定验算 根据《钢结构设计规范》GB50017,按无侧移框架柱计算。由于横梁A2B2的轴力很小,在计算柱长度系数时不考虑其影响。柱脚在横向为刚接,不考虑梁的组合效应,按纯钢梁计。 梁A2B2的截面为HN600×200×11×17其惯性矩为Ix=737490cm4 K1 I∑=∑Ibclb1.==0.43,K2=K1=0.43由《钢结构设计规范》附表3-1得lc4.39 lox0.691×450==17.6<120235fy=120235235=120,ix17.7 40 µx=0.691λx= 文天学院2012届本科生毕业设计(论文) 由 b=400/400=1.00>0.8,查《钢结构设计规范》附录C此柱截面为b类截面,h查得ϕx=0.977,框架为有侧移纯框架,βmx=1.0。 π2EA3.142×2.06×105×285.92×102 N===170432.74kN,22 1.1λx1.1×17.6 ' Ex对于第一组内力: NdβmxMd554.79×1031.0×211.81×106 +=+ 554.79ϕxAγW(1−0.8Nd)0.977×285.92×1021.05×4490×103×(1-0.8×)xx' NEx170432.74=.91Nmm2 NuβmxMu606.63×1031.0×948.97×106 +=+ 554.79ϕxAγW(1−0.8Nd)0.977×285.92×1021.05×4490×103×(1-0.8×)xx' NEx170432.74=223.5Nmm2≈f=215Nmm2, 工程上满足误差在5%范围内认为可以满足要求。(5) 弯矩作用平面外稳定验算 由《钢结构设计规范》附表3-1,柱平面外长细比计算: µy=0.683,则λy= 0.683×450 =30.13<120235fy=120235235=120, 10.2 由《钢结构设计规范》附录C按b类截面查得ϕy=0.935, λy2fy30.132235β=1.0 ϕb=1.07−⋅=1.07−×=0.985,框架为有侧移纯框架,tx4400023544000235截面影响系数η=1.0。 对于第一组内力: NdβtxMd554.79×1031.0×211.81×1062 +η=+1.0×=68.NmmϕyAϕbWx0.935×285.92×1020.985×4490×103 41 文天学院2012届本科生毕业设计(论文) NuβtxMu606.63×1031.0×156.53×106 +η=+1.0×=58.1Nmm2 23 ϕyAϕbWx0.935×285.92×100.985×4490×10 局部稳定翼缘板的宽厚比 b1191235==6.82<13=13,满足要求。t282352) 腹板的高厚比 对于第一组内力: σmaxσmin NdMdy1554.79×103211.81×106×1862 =+=+=61.77NmmAIx285.92×10293000×104NdMdy1554.79×103211.81×106×1862=−=−=−22.96NmmAIx285.92×10293000×104 应力梯度:α0=(σmax−σmin)/σmax=⎡⎣61.77−(−22.96)⎤⎦)/61.77=1.37<1.6腹板的允许高厚比: ⎡h0⎤235235=(16α+0.5λ+25)=(16×1.37+0.5×17.6+25)=55.75⎢⎥0xfy235⎣tw⎦高厚比 h0372 ==20.67<55.75,满足要求。tw18 对于第二组内力: σmaxσmin NdMdy1606.63×103156.53×106×186=+=+=52.52Nmm2 24 AIx285.92×1093000×10NdMdy1606.63×103156.53×106×186=−=−=−10.1Nmm2 24 AIx285.92×1093000×10 应力梯度:α0=(σmax−σmin)/σmax=(52.5+10.1)/52.5=1.19<1.6板的允许高厚比: ⎡h0⎤235235=(16×1.19+0.5×17.6+25)=52.84⎢⎥=(16α0+0.5λx+25)fy235⎣tw⎦高厚比 h0372 ==20.67<52.84,满足要求。因柱均采用同一截面形式,其它柱tw18 42 文天学院2012届本科生毕业设计(论文) 段的局稳可不用再计算。2.5.1.3(1)(2) 柱13-9 与柱5-1相同。 截面特性控制内力 根据内力组合表,强度验算可能由以下组合控制⎧Mu=−262.72kN⋅m,Md=154.25kN⋅m⎪ ⎨Nu=−227.57kN,Nd=−227.67kN⎪V=−65.65kN,V=−65.65kN⎩ud(3) 强度验算 截面无削弱,对第一组内力: ⎧Mu=−216.25kN⋅m,Md=149.46kN⋅m⎪ ⎨Nu=−283.62kN,Nd=−283.73kN⎪V=−81.27kN,V=−81.27kN⎩udNuMu227.67×103262.72×10622 +=+=63.69Nmm NuMu283.73×103216.25×10622 ,+=+=55.79Nmm 弯矩作用平面内的稳定验算 根据《钢结构设计规范》GB50017,按有侧移框架柱计算。由于横梁A3B3的轴力很小,在计算柱长度系数时不考虑其影响。柱脚在横向为刚接,不考虑梁的组合效应,按纯钢梁计。 梁A3B3的截面为HN600×200×11×17,其惯性矩为Ix=737490cm4。 K1 I∑=∑Ibclb1. 附表µx=1.65,==0.43,K2=K1=0.43《钢结构设计规范》 lc4.39 λx=由 lox1.65×450==41.95<120235fy=120235235=120,ix17.7 b=400/400=1.00>0.8,查《钢结构设计规范》附录C此柱截面为b类截面,h查得ϕx=0.1,框架为有侧移纯框架,βmx=1.0。 43 文天学院2012届本科生毕业设计(论文) π2EA3.142×2.06×105×285.92×102 N===29999.53kN,22 1.1λx1.1×41.95 ' Ex对于第一组内力: NdβmxMd227.67×1031.0×154.25×106 +=+ 227.67ϕxAγW(1−0.8Nd)0.1×285.92×1021.05×4490×103×(1-0.8×)xx' NEx29999.53=41.85Nmm2 NuβmxMu283.73×1031.0×216.25×106 +=+2 N283.73ϕxAγW(1−0.8d)0.1×285.92×101.05×4490×103×(1-0.8×)xx'NEx29999.53=57.36Nmm2 弯矩作用平面外稳定验算 纵向框架梁截面为HN400×200×8×13其惯性矩为Ix=22775cm4与柱刚接。 K1 I∑= ∑Ibcylb2×22775750==0.882,K2=0.882由《钢结构设计规范附表3-1lc31000?/450 得, µy=1.53,则λy= 1.53×450 =67.5<120235fy=120235235=120, 10.2 由《钢结构设计规范》附录C按b类截面查得 ϕy=0.766 , 67.52235 ϕb=1.07−⋅=1.07−×=0.966,框架为有侧移纯框架, 4400023544000235 λy2fyβtx=1.0。截面影响系数η=1.0。 对于第一组内力: NuβtxMu227.57×1031.0×262.72×1062 +η=+1.0×=70.96NmmϕyAϕbWx0.766×285.92×1020.966×4490×103 44 文天学院2012届本科生毕业设计(论文) NuβtxMu283.62×1031.0×216.25×106 +η=+1.0×=62.81Nmm2 23 ϕyAϕbWx0.766×285.92×100.966×4490×10 柱6-2 截面特性与柱5-1相同。控制内力 根据内力组合表,强度验算可能由以下组合控制 ⎧Mu=−233.33kN⋅m,Md=−366.49kN⋅m⎧Mu=4.69kN⋅m,Md=−9.40kN⋅m⎪⎪⎨Nu=−1365.91kN,Nd=−1377.02kN⎨Nu=−1785.10kN,Nd=−1785.18kN⎪V=1.61kN,V=1.61kN⎪V=2.17kN,V=2.17kN⎩ud⎩ud(3)强度验算 截面无削弱,对第一组内力: NdMd1377.02×103366.49×106+=+=125.90Nmm2 NuMu1785.18×1039.40×106 +=+=.43Nmm2 根据《钢结构设计规范》GB50017,按有侧移框架柱计算。由于横梁A1B1,B1C1的轴力很小,在计算柱长度系数时不考虑其影响。柱脚在横向为刚接,不考虑梁的组合效应,按纯钢梁计。 梁B1C1的截面为HN600×200×11×17,其惯性矩为Ix=737490cm4 K1= ∑I∑Ibclb2×73749/800==1.28,K2=10,由《钢结构设计规范》附表lc93000/8 lox1.12×8 ==41<120235fy=120235235=120,ix17.7 45 µx=1.12,则λx= 文天学院2012届本科生毕业设计(论文) 由 b=400/400=1.00>0.8,查《钢结构设计规范》附录C此柱截面为b类截面,h查得ϕx=0.5,框架为有侧移纯框架,βmx=1.0。 π2EA3.142×2.06×105×285.92×102 N===31405.86kN,22 1.1λx1.1×41 ' Ex对于第一组内力: NdβmxMd1377.02×1031.0×366.49×106 +=+ 1377.02ϕxAγW(1−0.8Nd)0.5×285.92×1021.05×4490×103×(1-0.8×)xx' NEx31405.86=134.37Nmm2 NuβmxMu1785.18×1031.0×9.40×106 +=+ ϕxAγW(1−0.8Nd)0.5×285.92×1021.05×4490×103×(1−0.8×1785.18)xx' NEx31405.86=71.85Nmm2 弯矩作用平面外稳定验算 纵向框架梁截面为HN400×200×8×13其惯性矩为Ix=22775cm4与柱刚接。柱脚在纵向也取刚接。 K1 I∑= ∑Ibcylb2×22775750==0.423,K2=10,由《钢结构设计规范》附表3-1,lc93000/8 1.34×8 =85.13<120235fy=120235235=120, 10.2 得µy=1.34,则λy= 由《钢结构设计规范》附录C按b类截面查得 λy2 fyϕy=0.654 , 85.132235β=1.0 ϕb=1.07−⋅=1.07−×=0.905,框架为有侧移纯框架,tx4400023544000235 截面影响系数η=1.0。 对于第一组内力: NdβtxMd1377.02×1031.0×366.49×106 +η=+1.0×=163.83Nmm2 23 ϕyAϕbWx0.654×285.92×100.905×4490×10 文天学院2012届本科生毕业设计(论文) 对于第二组内力: NuβtxMu1785.18×1031.0×9.04×106 +η=+1.0×=97.69Nmm2 23 ϕyAϕbWx0.654×285.92×100.905×4490×10 柱10-6 截面特性与柱5-1相同。控制内力 根据内力组合表,强度验算可能由以下组合控制⎧Mu=208.77kN⋅m,Md=−166.81kN⋅m⎪ ⎨Nu=−936.30kN,Nd=608.97kN⎪V=2.92kN,V=2.92kN⎩ud⎧Mu=14.24kN⋅m,Md=47.21kN⋅m⎪ ⎨Nu=−1157.75kN,Nd=776.84kN⎪V=4.98kN,V=−17.83kN⎩ud(3)强度验算 截面无削弱,对第一组内力: NdMd936.30×103208.77×106 +=+=77.03Nmm2 NuMu1157.75×10314.24×106 +=+=43.51Nmm2 根据《钢结构设计规范》GB50017,按有侧移框架柱计算。由于横梁 B2C2,B1C1的轴力很小,在计算柱长度系数时不考虑其影响。柱脚在横向为刚 接,不考虑梁的组合效应,按纯钢梁计。 梁B1C1,B2C2的截面均为HN600×200×11×17,其惯性矩为Ix=737490cm4 K1 I∑=∑Ibclb2×73749/800==0.,K2=lc93000/450 ∑I∑Ibclb=0.2由《钢结构设计规范》lc附表µx=1.53,则λx= lox1.53×450==38.9<120235fy=120235235=120,ix17.7 47 文天学院2012届本科生毕业设计(论文) 由 b=400/400=1.00>0.8,查《钢结构设计规范》附录C此柱截面为b类截面,h查得ϕx=0.903,框架为有侧移纯框架,βmx=1.0。 π2EA3.142×2.06×105×285.92×102 N===34888.25kN,22 1.1λx1.1×38.9 ' Ex对于第一组内力: NdβmxMd936.30×1031.0×208.77×106 +=+ 936.30ϕxAγW(1−0.8Nd)0.903×285.92×1021.05×4490×103×(1-0.8×)xx' NEx34888.25=81.84Nmm2 NuβmxMu1157.75×1031.0×14.24×106 +=+ ϕxAγW(1−0.8Nd)0.903×285.92×1021.05×4490×103×(1−0.8×1157.75)xx' NEx34888.25=47.95Nmm2 弯矩作用平面外稳定验算 纵向框架梁截面为HN400×200×8×13其惯性矩为Ix=22775cm4与柱刚接。柱脚在纵向也取刚接。 K1结 I∑= ∑I构 bcylb2×22775750==0.29,K2=lc93000/450设 计 规 范 ∑I∑Ibcylb2×22775/750 《钢==0.42由 lc93000/8附 表 3-1 , 得 》 µy=1.76,则λy= 1.76×450 =77.65<120235fy=120235235=120, 10.2 由《钢结构设计规范》附录C按b类截面查得ϕy=0.508, 77.652235β=1.0 ϕb=1.07−⋅=1.07−×=0.933,框架为有侧移纯框架,tx4400023544000235 λy2fy截面影响系数η=1.0。 对于第一组内力: 48 文天学院2012届本科生毕业设计(论文) NdβtxMd936.30×1031.0×208.77×106 +η=+1.0×=114.3Nmm2 23 ϕyAϕbWx0.508×285.92×100.933×4490×10 NdβtxMd1157.75×1031.0×14.24×106 +η=+1.0×=83.11Nmm2 23 ϕyAϕbWx0.508×285.92×100.933×4490×10 根据内力组合表,强度验算可能由以下组合控制 ⎧Mu=134.40kN⋅m,Md=−100.90kN⋅m⎪ ⎨Nu=−514.90kN,Nd=−514.90kN⎪V=5.93kN,V=5.93kN⎩ud(3) 强度验算 ⎧Mu=−2.50kN⋅m,Md=−8.42kN⋅m⎪ ⎨Nu=−585.17kN,Nd=−585.17kN⎪V=1.20kN,V=1.19kN⎩ud截面无削弱,对第一组内力: NuMu514.90×103134.40×10622 +=+=46.52Nmm NuMu585.17×1038.42×10622 +=+=22.25Nmm 弯矩作用平面内的稳定验算 根据《钢结构设计规范》GB50017,按有侧移框架柱计算。由于横梁A3B3,B3C3的轴力很小,在计算柱长度系数时不考虑其影响。柱脚在横向为刚接,不考虑梁的组合效应,按纯钢梁计。梁 A3B3的截面为HN600×200×11×17,其惯性矩为Ix=73749cm4。 49 文天学院2012届本科生毕业设计(论文) K1= ∑I∑Ibclb2×73749800==0.2lc93000450,K2=0.2,《钢结构设计规范》附表3-1,则λx= µx=1.53, lox1.53×450 ==38.9<120235fy=120235235=120,ix17.7 b=400/400=1.00>0.8,由h查《钢结构设计规范》附录C此柱截面为b类截面,查得ϕx=0.903,框架为有侧移纯框架,βmx=1.0。 π2EA3.142×2.06×105×285.92×102N===34888.25kN22 1.1λx1.1×38.9, ' Ex对于第一组内力: NdβmxMd514.90×1031.0×5.93×106 +=+ 514.90ϕxAγW(1−0.8Nd)0.903×285.92×1021.05×4490×103×(1-0.8×)xx' NEx34888.25=21.22Nmm2 NuβmxMu585.17×1031.0×8.42×106 +=+ ϕxAγW(1−0.8Nd)0.903×285.92×1021.05×4490×103×(1−0.8×585.17)xx' NEx34888.25=24.47Nmm2 弯矩作用平面外稳定验算 纵向框架梁截面为HN400×200×8×13,其惯性矩为Ix=22775cm4与柱刚接。 K1= ∑I∑Ibcylb2×22775750==0.882lc31000450 ,K2=0.882, 由《钢结构设计规范》附录C按b类截面查得 ϕy=0.766 , µy=1.53,则λy= λy2 1.53×450 =67.5<120235fy=120235235=120, 10.2 67.52235 ϕb=1.07−⋅=1.07−×=0.966, 4400023544000235框架为有侧移纯框架, fyβtx=1.0。截面影响系数η=1.0。对于第一组内力: 50 文天学院2012届本科生毕业设计(论文) NuβtxMu514.90×1031.0×5.93×106 +η=+1.0×=24.88Nmm2 23 ϕyAϕbWx0.766×285.92×100.966×4490×10 NuβtxMu585.17×1031.0×8.42×106 +η=+1.0×=28.66Nmm2 23 ϕyAϕbWx0.766×285.92×100.966×4490×10 采用组合楼板时,框架梁与楼板有可靠连接,能阻止梁上翼缘的侧向失稳可不进行整体稳定性验算;在支座负弯矩处,受压下翼缘处设侧向支撑。另外,本工程抗震设防烈度为7度,热轧H型钢梁的一般局部稳定能够得到保证,不必进行验算。因此框架梁只需进行强度和挠度验算。另外,主梁一般不考虑组合效应,按钢梁计算。2.5.2.1(1) 梁A1B1 截面特性 梁A1B1截面为HN600×200×11×17,其截面特性为:AS=131.71cm2 Ix=73749cmix=23.66cmWx=2458cmIy=2273cmiy=4.151cm(2) 控制内力 434 Wy=227.3cm 3 由内力组合表,强度验算由以下组合控制,最不利内力组合为一层梁中支座处内力: ⎧M=−429.23kN⋅m⎪ ⎨N=26.17kN⎪V=−168.10kN⎩(3) 强度验算 截面无削弱,按压弯构件验算正应力。另外,在次梁与主梁的连接处主梁腹板设置加劲肋,不必验算局部压应力。 梁翼缘承受的正应力验算第一组内力: 51 ⎧M=−365.63kN⋅m⎪ ⎨N=28.05kN⎪V=−171.50kN⎩ 文天学院2012届本科生毕业设计(论文) NM26.17×103429.23×106 +=+=168.3Nmm2 AnγxWx131.71×101.05×2458×10 第二组内力: NM171.50×103365.63×106 +=+=154.69Nmm2 AnγxWx131.71×101.05×2458×10满足要求。 梁腹板承受的剪力 Sx=bftfh−tf2 + (h−2tf)2 8 600−17(600−2×17)2 tw=200×17×+×11=14315.5mm3 28 第一组内力: VSx168.10×103×14315.522 满足要求。τ===29.66Nmm 第二组内力: VSx171.50×103×14315.5τ===30.26N/mm2 挠度验算(荷载的标准组合) 梁的最大挠度包括两部分,一部分由恒载产生,另一部分由活载产生,将两部分叠加即为总挠度。 图2.5.1梁 A1B1恒载挠度计算简图 从上图可得由集中恒载产生的挠度,用结构力学中的图乘法计算,均布恒载产生的挠度可用公式求得。 52 文天学院2012届本科生毕业设计(论文) 1⎡1⎤ ×149.19×2×4−×(90.81+149.19)⎢2⎥11611 υ集=∫MpMds=×⎢⎥=3.31mm1EI2.06×73749⎢1 +×149.19×2×4−×(128.83+149.19)⎥⎢⎥⎣26⎦5ql45×1.034×84 υ===0.363mm384EI384×2.06×73749 2 υG=υ1mm集+υq=3.31+0.363=3.67mm<[vt]=l/400=20 2q框架梁在荷载标准组合下的最大弹性挠度为,满足要求。活载作用下同样道理可验算: υT=υG+υQ=3.67+1.75=5.42mm<[υT]=l/400=20mm,满足要求。(5) 局部稳定性验算: 翼缘: b(200−11)/2==5.56<13,满足要求。t17 h0600−17==53<80,满足要求,不需设置加劲肋。tw11 腹板: (6)节点抗震验算 对于抗震设防的钢框架验算节点是否满足墙柱弱梁的要求,即是满足下式要求: ∑WPC(fyc− 式中: N)≥η∑WPbfybAcWPC,WPb柱和梁的塑性模量,N表示为柱轴向压力设计值,Ac表示柱截面面积,fyc, fyb表示柱和梁的钢材屈服强度, η表示强柱系数, 以底层中柱节点为例: (h−2t)2(400−2×28)2 Wpc=bt(h−t)+tw=400×28×(400−28)+×18=46912mm3 44 53 文天学院2012届本科生毕业设计(论文) (h−2t)2(600−2×17)2 Wpb=bt(h−t)+tw=200×17×(600−17)+×11=2863179mm3 44 ∑WPC(fyc− 满足要求。2.5.2.2 N1785.18)=2×46912×(235−)=2149KN•mAc285.92, >η∑WPbfyb=1.0×2×2863179×235=1345KN•m梁A2B2,A3B3,B1C1,B2C2,B3C3 梁A2B2,A3B3,B1C1,B2C2,B3C3的截面与梁A1B1的截面尺寸相同,而梁 A1B1的强度、挠度均满足要求,所以梁A2B2,A3B3,B1C1,B2C2,B3C3的强度 和挠度不用验算。 2.5.3次梁验算 次梁与主梁加劲肋采用铰接连接,按简支梁计算。 2.5.3.1标准层次梁CL01验算 (1)次梁截面特性 次梁截面为HN400×200×8×13,其截面特性为:AS=83.37cmIx=22775cmix=16.53cm Wx=1139cm3 Iy=1735cm4 iy=4.56cm Wy=173.5cm3 2 4 (2)荷载标准值计算 计算简图如图2.5.3: 图2.5.3次梁(CL01)恒载计算简图 按次梁为简支梁计算 54 文天学院2012届本科生毕业设计(论文) 次梁所受荷载标准值为:活载qQ=4.0×4.0=16.0KN/m 恒载qg=25×0.10×4.0=10.0KN/m 次梁所受荷载设计值为:q=1.2qg+1.4qQ =1.2×16.0+1.4×10.0=33.2KN/m 11 次梁所受最大弯矩M=ql2=×33.2×7.52=233.4KN•M8811 次梁所受剪力V=ql=×33.2×7.5=124.5KN22(3) 次梁CL01的控制内力(用荷载的基本组合):跨中最大弯矩设计值: GQMmax=1.2Mmax,k+1.4Mmax,k=233.4kN⋅mKN/m 支座A最大剪力设计值: GQVmax=1.2Vmax,k+1.4Vmax,k=124.5kN(4)强度验算 翼缘承受的正应力验算 M233.4×106σ===195.16Nmm2 h−tf(h−2tf)2400−13(400−2×13)2 Sx=bftf+tw=200×13×+×8=2976mm3 2828 VSx124.5×103×2976τ===43.94Nmm2 挠度验算(荷载的标准组合) 图2.5.4挠度计算简图 55 文天学院2012届本科生毕业设计(论文) 由恒载活载引起的挠度,计算简图如图2.5.4(结构力学图乘法): υq1= 11212l5 MMds=×(2××ql×××l)p∫EI2.06×22775382321217.55 =×(2×××102×××7.5)2.06×2277538232=1.56mm由梁自重及楼板荷载引起的挠度:5ql45×10×7.54υq2===8.78mm384EI384×2.06×22775 恒载引起的总挠度:vG=vq1+vq2=1.56+8.78=10.34mm活载引起的挠度: 5ql45×16×7.54 υQ===14.05mm<⎡υQ⎤=l/350=21.43mm,⎣⎦384EI384×2.06×22775满足要求。恒、活引起的挠度: vT=vG+vQ=10.34+21.43=31.77mm<[vT]=l/250=32mm满足要求。 其他次梁同样道理可以计算出均满足挠度限值要求。 2.6组合楼盖设计 本工程的楼、屋面均采用压型钢板组合楼板,它的设计和验算都应分施工阶段和使用阶段考虑,两阶段都应满足强度和刚度的要求。因为楼面与屋面的荷载相差较大,所以下面对楼板和屋面板分别进行设计和验算。 2.6.1楼板设计 组合楼板板跨为4.0m,为三跨连续板。组合楼板在钢梁上的支承长度为75mm。选用Q235钢的YX-75-230-690(Ⅱ)开口型槽口压型钢板,其构件特性为: 56 文天学院2012届本科生毕业设计(论文) 板厚t=0.8 mm,一个波距宽度内截面面积As=282.4mm2,截面惯性矩 Is=.31cm4/m,Ws=20.10cm3/m,形心到压型钢板板底的距离ht=31.92mm,压型钢板自重0.18kN/m2,强度设计值205N/mm2。压型钢板顶面上混凝土厚 hc=80mm,采用C20混凝土, α1=1.0,fc=9.6N/mm2,ft=1.1N/mm2,Ec=25500N/mm2。钢筋采用I级钢 2 f=210N/mmyHPB235,。组合板总高为130mm。施工阶段活载1.5N/mm2,使用 阶段活载2.0N/mm2。组合楼板示意图如图2.6.1: 压型钢板上翼缘必须焊横向短钢筋来保证压型钢板与混凝土共同作用。圆柱头焊钉穿过压型钢板焊于钢梁上,对混凝土板和梁之间的叠合面抗剪起重要作用。在组合板中,圆柱头焊钉只作为压型钢板与混凝土叠合面之间抗剪能力储备,按构造取。本结构板跨为4.0m,选用M16焊钉。 2.6.1.1荷载内力计算 (1) 施工阶段 恒载包括:钢筋和混凝土自重、压型钢板自重。活载包括:施工荷载。恒载: 图2.6.1组合楼板图 gk=6.440kN/m2 g1=γggk=1.2×=7.73kN/m2qk=1.5kN/m2 q1=γqqk=1.4×1.5=2.1kN/m2 活载: 施工阶段内力按弹性计算:三跨连续板(不需考虑荷载不利布置)。以1m宽板条为计算单元: 跨中正弯矩 57 文天学院2012届本科生毕业设计(论文) M1=0.08(g1+q1)l02=0.08×(4.3+2.1)×42=8.19kN⋅m支座负弯矩 22 M1−=0.1(g1+q1)l0=0.1×(4.3+2.1)×4=10.24kN⋅m支座剪力 V1=0.6(g1+q1)l0=0.6×(4.3+2.1)×4=15.36kN(2) 使用阶段 恒载包括:混凝土板自重、楼面做法、吊顶自重、压型钢板自重。恒载: gk=3.84kN/m2 g2=γggk=1.2×3.84=4.61kN/m2qk=2kN/m2 q2=γqqk=1.4×2=2.8kN/m2 活载: 使用阶段内力按塑性计算:压型钢板顶面上混凝土厚hc=80mm<100mm。以1m宽板条为计算单元: 跨中正弯矩:按简支单向板计算 11 M2=(g2+q2)ln2=×(4.61+2.8)×3.852=13.73kN⋅m88 支座负弯矩:按固端板计算 11 (g2+q2)ln2=×(4.61+2.8)×3.852=9.15kN⋅m1212支座剪力 −M2= V2=0.6(g2+q2)ln=0.6×(4.61+2.8)×3.85=17.12kN取计算单元宽度为波距:b=230mm时的内力:正截面跨中弯矩:M=13.73×230/1000=3.16kN⋅m支座负弯矩:支座剪力: M=9.15×230/1000=2.10kN⋅mV=17.12×230/1000=3.94kN58 文天学院2012届本科生毕业设计(论文) 2.6.1.2压型钢板验算(施工阶段) Is.31==27.99cm3ht3.19Is.31 ==76.99cm3 hs−ht1.16 Ws1=Ws2= 抗弯验算 Mu=Ws1f=27.99×103×205=5.74kN⋅m,满足要求。挠度验算 41pkl01(3.58+1.5)×44×10124000ω==×=5.49mm<ω=min(,20)=20mm[]54 140EsIs1402.06×10×.31×10180 满足要求。 2.6.1.3组合板验算(使用阶段) (1) 正截面抗弯验算 组合板的有效高度:h0=h−ht=75+80−31.92=123.08mm正截面抗弯验算 Asf=282.4×205×0.8=46.31kNα1fcbhc=1.0×9.6×0.8×230×80=141.31kN由于Asf<α1fcbhc,因此组合板的塑性中和轴在混凝土中: x= Asf46.31 ==26.22mm<0.55h0=0.55×123.08=67.69mmα1fcb1.0×9.6×0.8×230 取x=26.22mmx26.22 Mu=0.8α1fcbx(h0−)=0.8×1.0×0.8×9.6×26.22×230×(123.08−)=4.07kN⋅m22 >M=0.9kN⋅m满足要求。(2) 斜截面抗剪验算 Vu=0.7ftbh0=0.7×1.1×230×123.08=21.80kN>V=2.11kN,满足要求。 59 文天学院2012届本科生毕业设计(论文) (3)支座负弯矩配筋计算 h0′=hc−as=80−25=55mm2.10×106 αs===0.31422 α1fcbh0′1.0×9.6×230×55 M1+1−2αs1+1−2×0.314γs===0.805 22 6 M2.1×10 As′===255.86mm2 γsfyh0′0.805×210×55选用6/8@125,As=314mm2>255.86mm2。 ρ=(4) As314f=×100%=1.71%>ρmin=max(0.45t×100%,0.2%)=0.24%bhc230×80fy挠度验算(荷载的标准组合) 根据变形相等的原则,将混凝土材料转化为等效的钢材。 Es2.06×105 αE===8.08 Ec2.55×104 荷载标准组合下换算成钢截面后的组合截面特征值:组合板截面中和轴到板顶的距离 x== 1b(−As+As2+2Ash0)b/αEαE1250(−256+2562+2××256×103.5)=33.93mm250/8.088.08组合截面惯性矩 1b3 x+Is+As(h0−x)2 3αE1250=××33.933+9.86×104+256×(103.5−33.93)2=1.74×106mm4 38.08 I0= 荷载准永久组合下换算成钢截面后的组合截面特征值:组合截面中和轴到板顶的距离 x== 1b(−As+As2+2Ah)b/(2αE)2αEs01250(−256+2562+2××256×103.5)=44.27mm250/(2×8.08)2×8.0860 文天学院2012届本科生毕业设计(论文) 截面惯性矩 I0q= 1b3 x+Is+As(h0−x)2 32αE1250=××44.273+9.86×104+256×(103.5−44.27)2=1.44×106mm4 32×8.08荷载标准组合下挠度 1qkl41(3.38+2.0)×2.054×0.25×1012 ωk==×=0.47mm56 140EsI01402.06×10×1.74×10荷载准永久组合下的挠度 41qql1(3.38+0.4×2.0)×2.054×0.25×1012 ωq==×=0.44mm140EsI0q1402.06×105×1.44×106 容许挠度 [ω]= (5) ln2050 ==5.69mm360360 自振频率验算 仅考虑恒载作用时组合板的挠度 gk′=3.38×1× 250 =0.845kN/m1000 4 1gk′ln10.845×2.054×1012 ω==×=0.36mm=0.036cm56 140EsI0q1402.06×10×1.44×10 自振频率 f= 11==29.6Hz>15Hz0.178ω0.1780.036满足要求。 2.6.2屋面板设计 组合楼板板跨为4.0m,为三跨连续板。组合楼板在钢梁上的支承长度为75mm。选用Q235钢的YX-75-230-690(Ⅱ)开口型槽口压型钢板,其构件特性为:板厚t=0.8 mm,一个波距宽度内截面面积As=282.4mm2,截面惯性矩 Is=.31cm4/m,Ws=20.10cm3/m,形心到压型钢板板底的距离ht=31.92mm,压型钢板自重0.18kN/m2,强度设计值205N/mm2。压型钢板顶面上混凝土厚 61 文天学院2012届本科生毕业设计(论文) hc=80mm,采用C20混凝土, α1=1.0,fc=9.6N/mm2,ft=1.1N/mm2,Ec=25500N/mm2。钢筋采用I级钢 2 f=210N/mmyHPB235,。组合板总高为130mm。施工阶段活载1.5N/mm2,使用 阶段活载2.0N/mm2。 压型钢板上翼缘必须焊横向短钢筋来保证压型钢板与混凝土共同作用。圆柱头焊钉穿过压型钢板焊于钢梁上,对混凝土板和梁之间的叠合面抗剪起重要作用。在组合板中,圆柱头焊钉只作为压型钢板与混凝土叠合面之间抗剪能力储备,按构造取。本结构板跨为4.0m,选用M16焊钉。 2.6.2.1荷载和内力计算 (1) 施工阶段 恒载包括:钢筋和混凝土自重、压型钢板自重。活载包括:施工荷载。 gk=6.44kN/m2 恒载: g1=γggk=1.2×6.44=7.73kN/m2qk=1.5kN/m2 2 q=γq=1.4×1.5=2.1kN/m1qk活载: 施工阶段内力按弹性计算:三跨连续板(不需考虑荷载不利布置)。以1m宽板条为计算单元:跨中正弯矩 M1=0.08(g1+q1)l02=0.08×(7.73+2.1)×42=12.58kN⋅m支座负弯矩 2 M1−=0.1(g1+q1)l0=0.1×(7.73+2.1)×42=15.73kN⋅m支座剪力 V1=0.6(g1+q1)l0=0.6×(7.73+2.1)×4=23.59kN(2) 使用阶段 恒载包括:混凝土板自重、楼面做法、吊顶自重、压型钢板自重。 62 文天学院2012届本科生毕业设计(论文) 恒载: gk=7.73kN/m2 g2=γggk=1.2×7.73=9.28kN/m2qk=2kN/m2 q2=γqqk=1.4×2=2.8kN/m2 活载: 使用阶段内力按塑性计算:压型钢板顶面上混凝土厚hc=80mm<100mm。以1m宽板条为计算单元:跨中正弯矩:按简支单向板计算 11 M2=(g2+q2)ln2=×(9.28+2.8)×3.852=22.37kN⋅m88支座负弯矩:按固端板计算 − M2= 112 (g2+q2)ln=×(9.28+2.8)×3.852=14.92kN⋅m1212 支座剪力 V2=0.6(g2+q2)ln=0.6×(9.28+2.8)×3.85=27.90kN取计算单元宽度为波距:b=250mm时的内力:正截面跨中弯矩:M=22.37×230/1000=5.15kN⋅m支座负弯矩:支座剪力: M=14.92×230/1000=3.43kN⋅mV=24.32×230/1000=5.59kN2.6.2.2压型钢板验算(施工阶段) Ws1=Ws2 Is.31==27.99cm3ht3.19Is.31===76.99cm3 hs−ht1.16 抗弯验算 Mu=Ws1f=27.99×103×205=4.67kN⋅m,满足要求。挠度验算 4 1pkl01(9.28+2.8)×44×10124000ω==×=12mm<ω=min(,20)=20mm[]54 140EsIs1402.06×10×.31×10180 63 文天学院2012届本科生毕业设计(论文) 满足要求。 2.6.2.3组合板验算(使用阶段) (1) 正截面抗弯验算 组合板的有效高度:h0=h−ht=75+80−31.92=123.08mm正截面抗弯验算 Asf=282.4×205×0.8=46.31kNα1fcbhc=1.0×11.9×0.8×230×80=175.17kN由于Asf<α1fcbhc,因此组合板的塑性中和轴在混凝土中: x= Asf46.31 ==21.15mm<0.55h0=0.55×123.08=67.69mmα1fcb1.0×11.9×0.8×230 取x=21.15mmx21.15 Mu=0.8α1fcbx(h0−)=0.8×1.0×0.8×11.9×21.15×230×(123.08−)=4.17kN⋅m22 >M=3.43kN⋅m满足要求。(2) 斜截面抗剪验算 Vu=0.7ftbh0=0.7×1.27×230×123.08=25.17kN>V=5.59kN,满足要求。(3)支座负弯矩配筋计算 h0′=hc−as=80−25=55mm3.43×106 αs===0.41422 α1fcbh0′1.0×11.9×230×55 M1+1−2αs1+1−2×0.414γs===0.707 22 6 M3.43×10 As′===420mm2 γsfyh0′0.707×210×55选用 8/10@125,As=515mm>420mm。 2 2 ρ= As515f=×100%=2.8%>ρmin=max(0.45t×100%,0.2%)=0.24%bhc230×80fy 文天学院2012届本科生毕业设计(论文) (4)挠度验算(荷载的标准组合) 根据变形相等的原则,将混凝土材料转化为等效的钢材。 Es2.06×105 αE===7.3 Ec2.8×10 荷载标准组合下换算成钢截面后的组合截面特征值:组合板截面中和轴到板顶的距离 x== 1b(−As+As2+2Ash0)b/αEαE1230(−282.4+282.42+2××282.4×123.08)=38.98mm230/7.367.36组合截面惯性矩 1b3 x+Is+As(h0−x)2 3αE1230=××38.983+8.93×104+282.4×(123.08−38.98)2=2.73×106mm4 37.36 I0= 荷载准永久组合下换算成钢截面后的组合截面特征值:组合截面中和轴到板顶的距离 x== 1b(−As+As2+2Ah)b/(2αE)2αEs01230(−282.4+282.42+2××282.4×123.08)=51.03mm230/(2×7.36)2×7.36截面惯性矩 I0q= 1b3 x+Is+As(h0−x)2 32αE1230=××51.033+9.31×104+282.4×(123.08−51.03)2=2.25×106mm4 32×7.36荷载标准组合下挠度 1qkl41(9.28+2.8)×3.854×0.25×1012 ωk==×=8.43mm56 140EsI01402.06×10×2.73×10荷载准永久组合下的挠度 41qql1(7.73+2.1)×3.854×0.25×1012 ωq==×=8.32mm140EsI0q1402.06×105×2.25×106 65 文天学院2012届本科生毕业设计(论文) 容许挠度 ln3850==10.69mm360360 (5)自振频率验算 [ω]= 仅考虑恒载作用时组合板的挠度 gk′=9.28×1× 230 =2.13kN/m1000 4 1gk′ln12.13×3.854×1012 ω==×=1.87mm140EsI0q1402.06×105×2.25×106 自振频率 f= 11==41.05Hz>15Hz0.178ω0.1780.0187满足要求。 2.7框架连接设计 框架连接设计包括主梁与柱、次梁与主梁的连接及柱脚设计。连接设计必须满足强度和刚度的要求,同时还需与计算简图一致。另外,还要尽量简化构造,方便施工。本设计中,主梁与柱为刚接方案,次梁与主梁为铰接连接,次梁通过主梁腹板加劲肋与主梁相连,为方便压型钢板铺设,次梁和主梁上表面齐平放置。框架的柱脚为双向刚接,本工程只有3层,又处于7度抗震设防区,侧向刚度要求不高,采用外露式平板柱脚。 2.7.1主梁与柱的连接设计 主梁与柱采用刚接方案,由于抗震设防烈度为7度,栓焊连接方式完全能满足要求,且加工、安装方便,因此采用这种方式。采用《高层民用钢结构技术规程》(JGJ99)推荐的“精确设计法”,即腹板要承担全部剪力和按惯性矩比例分配的弯矩。由于翼缘采用对接焊缝连接为等强设计,翼缘焊缝不必计算。在计算腹板承担的弯矩时惯性矩为扣除焊缝通过孔后的截面(梁上、下翼缘焊缝通过孔的尺寸取相同)。 66 文天学院2012届本科生毕业设计(论文) 2.7.1.1主梁A1B1与柱栓焊连接设计 主梁A1B1与柱A0A1、柱B0B1的连接节点采用同一节点设计,因为主梁A1B1左右截面的控制内力相差不大,且右截面控制内力较大,选取梁右截面的控制内力。⎧M=−329.23kN⋅m⎪ ⎨N=26.17kN⎪V=−168.10kN控制内力⎩(1) 计算指标 高强螺栓采用8.8级M20,连接为摩擦型,孔径d0=22mm,摩擦面做喷砂处理,摩擦面抗滑移系数µ=0.45,螺栓预拉应力为 P=150kN; 翼缘钢材: t=17mm:f=215N/mm2,fV=125N/mm2,fy=235N/mm2,fu=375N/mm2;腹板钢材: t=11mm:f=215N/mm2,fv=125N/mm2,fy=235N/mm2; 焊缝:焊条为E43系列,手工焊, 图2.7.1梁柱刚接计算图示 ww2 f=f=215N/mm,t对接焊缝:cw2f=160N/mm;f角焊缝: (2)螺栓布置及计算1)按螺栓布置要求:螺栓至连接板端部b≥2d0=2×22=44mm,取55mm,螺栓孔的最小边距≥1.5d0=1.5×22=33mm67 文天学院2012届本科生毕业设计(论文) (20mm为安装缝隙),取35mm;h1=578mm;h2=h−35×2=530mm;螺栓间距a≥3d0=3×22=66mm,且a≤8d0=176mm2)判断是否需要双排螺栓翼缘的塑性截面模量: Wpf=bftf(h−tf)=200×17×(600−17)=1982200mm3梁全截面塑性截面模量: Wpb=bftf(h−tf)+twh12/4=1982200+11×5782/4=2900931mm3 Wpf=1982200mm3<0.7Wpb=0.7×2900931=2030652mm3,梁腹板与柱的连接采用双排。 3)一个高强螺栓的抗剪承载力设计值 bNV=0.9nfµP=0.9×1×0.45×125=50.63kN根据剪力确定螺栓数目 n= V=168.10/50.63=3.32,据设计经验,设每排螺栓4个,应设2排,共8个。bNV螺栓栓距a=70mm,线距a1=110mm。节点示意图如图2.7.1(3) 节点弹性设计计算 梁腹板净惯性矩(扣除焊缝通过孔高上下各35mm)为: Iw0 11×5303==13.6×107mm4 12 梁翼缘惯性矩为: 11×5803 If=I−(Iw0+Ib0)=73749×10−=5.6×108mm4 12 4 式中Ib0为焊缝通过孔惯性矩。则腹板分担的弯矩: Mw0 Iw013.6×107 =M=×329.23=.33kN⋅m87 If+Iw05.6×10+13.6×10 单个螺栓承受的剪力为: 68 文天学院2012届本科生毕业设计(论文) V=168.10/8=21.02kNn螺栓承受的扭矩为: VN1y= T=Mw0−Ve=.33−168.10×0.095=48.36kN⋅m在T作用下受力最大螺栓承受的剪力: Ty148.36×165×103N===33.55kN2222 2×∑(xi+yi)2×(4×50+4×165)T1xTx148.36×50×103 N===10.17kN2×∑(xi2+yi2)2×(4×502+4×1652) T1y则 bN1=(N1Tx)2+(N1Vy+N1Ty)2=33.552+(21.02+10.17)2=45.80kN 连接板净截面与梁腹板净截面相等计算t: t= tw(h1−nwd0)11×(578−4×22) ==12.19mm式中h1、h2分别为腹 h2−nwd0530−4×22 板、连接板的高度;nw为单排螺栓数。根据螺栓间距最大要求确定连接板厚度t: a=110/12=9.17mm12 根据支承板的宽度bs,求连接板的厚度t:t≥ bs=(15+45+100+45)/15=13.67mm15 综合以上数值,并考虑腹板弯矩去连接板的厚度t=14mm,则t≥ f=215N/mm2,fv=125N/mm2。 2)验算连接板的强度:验算连接板的抗剪强度: 螺栓连接处的连接板净截面面积: An=(h2−nwd0)t=(530−4×22)×14=6188mm2 69 文天学院2012届本科生毕业设计(论文) τ= V=168.1×103/6188=27.17N/mm2 th2/12−2td()14×5303/12−2×14×22×70200.5aWn===4043mm3 h2/2530/2 σ=Mw0/Wn=.33×106/4043=99.88N/mm2 σ折=σ2+3τ2=185.112+3×54.672=193.01N/mm2<1.1f=1.1×215=236.5N/mm2满足要求。(5) 连接板与柱翼缘相连的双面角焊缝强度验算:1)焊脚尺寸的确定按构造要求,求hf, hmin=1.5tmax=1.5max(14,16)=6mmhmax=1.2tmin=1.2min(14,16)=16.8mm焊脚尺寸hf取 1 2 hf=10mm。 2)焊缝强度验算(按弯剪计算) σMf6Mw06×.33×106===98.14N/mm2 222helw2×0.7×10×530 168.1×103 τ===22.65N/mm2 he∑lw0.7×10×1060 VfV22(σMτV(98.14/1.22)2+22.652=83.57N/mm2 节点域验算: 1)节点域的柱腹板厚度验算: 70 文天学院2012届本科生毕业设计(论文) hb=h梁−2tf=600−2×17=566mmhc=h柱−2tcf=400−2×28=344mmtw=10mm≈(hb+hc)/90=(566+344)/90=10.11mm满足要求。 2)节点域的抗剪强度验算: Mb1+Mb2(360−329)×10τ===15.92N/mm2 满足要求,式中Vp为节点域腹板体积(VP=hbhctw)。 2.7.1.2主梁A3B3与柱栓焊连接设计 主梁 A3B3左右截面最大控制内力相差不大,此梁的最大控制内力 ⎧M=−325.92kN⋅m⎪ ⎨N=−99.12kN⎪V=−163.23kN⎩ 图2.7.2梁柱刚接计算图示 相比较可得,梁A1B1的内力较A3B3的内力大(N不起控制作用),且起控制作用 的M、V相差很小(轴力N不予考虑)分析如下:∆M=329.23−325.92=3.31kN⋅m,∆V=168.1−163.23=4.87kN综上,且考虑方便施工,主梁主梁 A3B3与柱的节点连接设计采用与A1B1与柱连接设计相同的方案。 71 文天学院2012届本科生毕业设计(论文) 此节点示意图如图2.7.2: 2.7.1.3主梁B1C1与柱栓焊连接设计 主梁B1C1与柱B0B1、柱C0C1的连接节点采用同一节点设计,因为主梁B1C1左右截面的控制内力相差不大,选取左截面的控制内力。 ⎧M=−412.79kN⋅m⎪ ⎨N=24.87kN⎪V=108.4kN⎩ 控制内力(1) 计算指标 高强螺栓采用8.8级M20,连接为摩擦型,孔径d0=22mm,摩擦面做喷砂处理,摩擦面抗滑移系数µ=0.45,螺栓预拉应力为P=125kN; t=11mm:f=215N/mm2,fV=125N/mm2,fy=235N/mm2, 2 f=375N/mm;翼缘钢材u腹板钢材 t=7mm:f=215N/mm2,fv=125N/mm2,fy=235N/mm2; ww2 f=f=215N/mm,ct焊缝:焊条为E43系列,手工焊,对接焊缝 角焊缝(2) ffw=160N/mm2; 螺栓布置及计算 1)按螺栓布置要求: 螺栓至连接板端部b≥2d0=2×22=44mm,取45mm,c至少取tf+20=31mm(20mm为安装缝隙),取35mm;h;h−78×21=578mm2=h=530mm;螺栓间距a≥3d0=3×22=66mm,且a≤8d0=176mm2)判断是否需要双排螺栓翼缘的塑性截面模量: Wpf=bftf(h−tf)=200×17×(600−17)=1982200mm3梁全截面塑性截面模量: Wpb=bftf(h−tf)+twh12/4=1982200+11×5782/4=2900931mm3 72 文天学院2012届本科生毕业设计(论文) Wpf=1982200mm3<0.7Wpb=0.7×2900931=2030652mm3 接采用双排。3) 一 个 高 强 螺 栓 的 抗 剪 承 载 ,梁腹板与柱的连 力设计值 bNV=0.9nfµP=0.9×1×0.45×125=50.63kNVn=b=108.4/50.63=2.14 NV根据剪力确定螺栓数目,据设计经验,设螺栓4个,单排。螺栓间距a=110mm<8d0=176mm,满足。节点示意图如图2.7.3算图示(3) 节点弹性设计计算 梁柱刚接计 梁腹板净惯性矩(扣除焊缝通过孔高上下各35mm)为: Iw0 11×5303 ==13.6×107mm4 12 梁翼缘惯性矩为: 11×5803 If=I−(Iw0+Ib0)=73749×10−=5.6×108mm4 12 4 式中Ib0为焊缝通过孔惯性矩。则腹板分担的弯矩: Mw0 Iw013.6×107 =M=×412.79=80.67kN⋅m87 If+Iw05.6×10+13.6×10 单个螺栓承受的剪力为: V=108.4/8=13.55kNn螺栓承受的扭矩为: VN1y= T=Mw0−Ve=80.67−108.4×0.095=70.36kN⋅m在T作用下受力最大螺栓承受的剪力: Ty170.36×165×103N===48.8kN2222 2×∑(xi+yi)2×(4×50+4×165)T1xTx170.36×50×103 N===14.7kN2222 2×∑(xi+yi)2×(4×50+4×165) T1ybN1=(N1Tx)2+(N1Vy)2=48.82+14.72=50.99kN≈NV=50.63kN满足要求。 73 文天学院2012届本科生毕业设计(论文) (4)连接板厚度的确定及强度验算(采用单侧连接板) 1)连接板厚度的确定: 连接板净截面与梁腹板净截面相等计算t: t= tw(h1−nwd0)11×(578−4×22) ==12.19mmh2−nwd0530−4×22式中h1、h2分别为腹 板、连接板的高度;nw为单排螺栓数。根据螺栓间距最大要求确定连接板厚度t: a=110/12=9.17mm12 根据支承板的宽度bs,求连接板的厚度t:t≥ bs=(15+45+100+45)/15=13.67mm15 综合以上数值,并考虑腹板弯矩去连接板的厚度t=14mm,t≥ 22 f=215N/mm,f=125N/mmv则。 2)验算连接板的强度:验算连接板的抗剪强度: 螺栓连接处的连接板净截面面积: An=(h2−nwd0)t=(530−4×22)×14=6188mm2τ= V=108.4×103/6188=17.51N/mm2 th23/12−2td0a214×5303/12−2×14×22×1102Wn===627306mm3 h2/2530/2 σ=Mw0/Wn=80.67×106/627306=128.60N/mm2 连接板与柱翼缘相连的双面角焊缝强度验算: 74 文天学院2012届本科生毕业设计(论文) 1)焊脚尺寸的确定按构造要求,求hf: hmin=1.5tmax=1.5max(14,16)=6mmhmax=1.2tmin=1.2min(14,16)=16.8mm焊脚尺寸hf取 12 hf=10mm。 2)焊缝强度验算(按弯剪计算) σMf6Mw06×80.67×106===123N/mm2 222helw2×0.7×10×530 108.4×103 τ===14.61N/mm2 he∑lw0.7×10×1060 VfV22(σMτV(123/1.22)2+14.612=101.87N/mm2f/βf)+(f)=
因篇幅问题不能全部显示,请点此查看更多更全内容